U-7517M-10 OPC UA I/O Module, 10/20-ch Analog Input with PoE

Informations sur le produit "U-7517M-10 OPC UA I/O Module, 10/20-ch Analog Input with PoE"

U-7517M-10 CR is an OPC UA I/O module for collecting voltage and current signals and passing them to cloud platforms or field control systems. Its 16-bit analog inputs can be set in software to 10 differential or 20 single-ended channels, with ranges selected by jumper from ±150 mV up to 4 to 20 mA.

The built-in dual-port switch lets modules be daisy-chained, which reduces cabling and the number of switch ports needed. Power can be taken from a PoE network under IEEE 802.3af (Class 3), or from a +12 ~ +48 VDC terminal block, so one cable can carry both data and power.

Communication runs over OPC UA Server/Client, MQTT Client and RESTful API, and these can operate at the same time. Scaling, IF/THEN/ELSE rules, scheduled actions and I/O trigger messages are configured through the built-in web interface, with no additional app needed.

Applications

  • Sending analogue measurements to cloud systems for display, analysis or strategy
  • Feeding analogue readings into field control systems over OPC UA or MQTT
  • Local rule-based control of I/O and virtual points
  • Scheduled execution of control rules at set times
Product type: OPC UA I/O Module
Interface: Ethernet
Protocol: MQTT, OPC UA, RESTful API
Analog inputs: 10/20
Ports: 2
PoE: IEEE 802.3af (Class 3)
Isolation: 2500 VDC
Power input: +12 ~ +48 VDC
Operating temperature: -25 ~ +75 °C
Mounting: DIN-rail

Specifications

Software
Protocol• OPC UA Server / Client
• MQTT Client
• RESTful API
Function• Web Interface for Configuration
• Scaling
• Security
• Rule Setting
• Schedule
• Event Log
• IoTstar Setting
CPU Module
CPU32-bit CPU (400 MHz)
Watchdog TimerModule, Communication (Programmable)
Isolation
2-way IsolationI/O: 2500 VDC
EMS Protection
EFT (IEC 61000-4-4)±2 kV for Power Line
ESD (IEC 61000-4-2)±4 kV Contact for each terminal
±8 kV Air for random point
Surge (IEC 61000-4-5)±2 kV for Power Line
LED Indicators
StatusRun, Ethernet, I/O
Analog Input
Channels10 differential or 20 single-ended
(Note1), software selectable
TypeVoltage, Current
Range±150 mV, ±500 mV, ±1 V, ±5 V, ±10 V,
±20 mA, 0 to 20 mA, 4 to 20 mA
(Jumper Selectable)
Resolution16-bit
AccuracyNormal Mode: ±0.1%
Fast Mode: ±0.5% or better
Sampling RateNormal Mode: 10 samples/second (Total)
Fast Mode: 50 samples/second (Total)
Input ImpedanceVoltage: 2 MΩ (Differential), 1 MΩ (Single-ended)
Current: 125 Ω
Common Mode Rejection86 dB (min.)
Normal Mode Rejection100 dB
Common Voltage Protection±200 VDC
Overvoltage ProtectionDifferential: 240 Vrms
Single-ended: 150 Vrms
Overcurrent Protection50 mA at 110 VDC (max.)
Individual Channel ConfigurationYes
Open Wire DetectionFor 4 ~ 20 mA only
Zero Drift±20 μV/°C
Span Drift±25 ppm/°C
Isolation±400 VDC, Virtual Channel to Channel Isolation
Ethernet
Ports2 x RJ-45, 10/100 Base-TX, Swtich Ports
PoEYes
LAN bypassYes
Access ControlID, Password and IP Filter
Power
Reverse Polarity ProtectionYes
Consumption5.5 W
Powered from PoEIEEE 802.3af, Class3
Powered from Terminal Block+12 ~ +48 VDC
Mechanical
Dimensions (mm)97 x 120 x 47 (W x L x H)
InstallationDIN-Rail mounting
Environment
Operating Temperature-25 ~ +75 °C
Storage Temperature-30 ~ +80 °C
Humidity10 ~ 90% RH, Non-condensing

Specifications as published by the manufacturer. Subject to change.