PM-3114-240P-CPS CANopen Single-Phase Power Meter, 4 Loops, 200 A CT
Single-phase 4-loop power meter with a CANopen interface, 200 A clip-on CT (24 mm aperture) and 4 m wire leads, for real-time energy monitoring on 1P2W circuits.
- Four-loop single-phase energy analysis for 1P2W circuits, with two independent loop reference voltages
- CANopen protocol with DIP-switch selectable baud rate: 125 k (default), 250 k, 500 k or 1 M
- Clip-on 200 A CT with 24 mm inside diameter and 4 m wire lead, four supplied
- True RMS measurement of voltage, current, active, apparent and reactive power, energy and power factor
- Accuracy better than 0.5% for W (PF=1); data update rate of 1 second
- Two Form A power relay outputs for alarm or switching functions
€672.00 per piece
| 1-9 pcs | €672.00 | |
|---|---|---|
| 10-30 pcs | €638.00 | −5 % |
| 31+ pcs | €604.00 | −10 % |
Product information "PM-3114-240P-CPS CANopen Single-Phase Power Meter, 4 Loops, 200 A CT"
The PM-3114-240P-CPS CR is a DIN-rail power meter that measures four single-phase loops and reports the results over CANopen. It suits engineers who need true RMS voltage, current, power, energy and power factor data from a single compact module, with the current read through clip-on transformers rather than hard-wired connections.
Each loop is measured through a 24 mm clip-on CT rated 0.15 A ~ 200 A, and the four CTs are supplied with 4 m leads. The meter accepts 10 ~ 300 VAC input at 50/60 Hz and updates its data every second. Accuracy for W is better than 0.5% at PF=1.
- Active, apparent and reactive power and energy, plus frequency, are available for monitoring.
- Two Form A power relay outputs (5 A @ 250 VAC or 5 A @ 30 VDC) can drive sirens or lights for alarm signalling.
Applications
- Generator monitoring
- Switchgear distribution systems
- Energy management
| Product type: | Power meter |
|---|---|
| Protocol: | CANopen |
| Relay outputs: | 2 |
| Power input: | +12 ~ 48 VDC |
| Operating temperature: | -20 ~ +70 °C |
| Mounting: | DIN-rail |
| Housing: | Plastic |
Specifications
| AC Power Measurement | |
|---|---|
| Wiring | 1P2W-1CT |
| Loops | 1-phase: 4 |
| Input Voltage | 10 ~ 300 V |
| Input Current | PM-3114-100-CPS: CTØ10 mm (0.05 A ~ 60 A) PM-3114-100P-CPS: CTØ10 mm (0.05 A ~ 60 A) PM-3114-160-CPS: CTØ16 mm (0.1 A ~ 100 A) PM-3114-160P-CPS: CTØ16 mm (0.1 A ~ 100 A) PM-3114-240-CPS: CTØ24 mm (0.15 A ~ 200 A) PM-3114-240P-CPS: CTØ24 mm (0.15 A ~ 200 A) |
| Input Frequency | 50/60 Hz |
| W Accuracy | Better than 0.5% (PF=1) |
| Power Parameter Measurement | True RMS voltage (Vrms), True RMS current (Irms), Active Power (kW), Active Energy (kWh), Apparent Power (kVA), Apparent Energy (kVAh), Reactive Power (kVAR), Reactive Energy (kVARh), Power Factor (PF), Frequency |
| Data Update Rate | 1 Second |
| Relay Output | |
| Channels | 2 |
| Type | Power Relay |
| Contact Rating | Form A: 5 A @ 250 VAC 5 A @ 30 VDC |
| CANopen | |
| Baud Rate | 125 k (default), 250 k, 500 k, 1 M; DIP Switch Selectable |
| Protocol | CANopen |
| Power | |
| Input Range | +12 ~ 48 VDC |
| Consumption | 2W |
| Mechanical | |
| Casing | Plastic |
| Dimensions (mm) | 33 x 127 x 100 (W x L x H) |
| Installation | DIN-Rail Mounting |
| Environment | |
| Operating Temperature | -20 ~ +70 °C |
| Storage Temperature | -25 ~ +80 °C |
| Humidity | 10 ~ 90% RH, Non-condensing |
Specifications as published by the manufacturer. Subject to change.