PM-3114-100P-CPS Single-Phase Power Meter, 4-Loop CANopen with 60 A CT
CANopen single-phase power meter with four loops and clip-on 60 A CTs (10 mm aperture, 4 m leads) for real-time energy monitoring on 1P2W circuits.
- Four-loop single-phase energy analysis for 1P2W wiring with true RMS measurement
- Clip-on 60 A CTs, 10 mm inside diameter, 4 m wire lead, for 0.05 A to 60 A input current
- W accuracy better than 0.5% (PF=1)
- Input voltage range 10 to 300 VAC
- Two Form A power relay outputs rated 5 A @ 250 VAC or 5 A @ 30 VDC
- CANopen interface with DIP switch selectable baud rate: 125 k (default), 250 k, 500 k or 1 M
€368.00 per piece
| 1-9 pcs | €368.00 | |
|---|---|---|
| 10-30 pcs | €349.00 | −5 % |
| 31+ pcs | €331.00 | −10 % |
Product information "PM-3114-100P-CPS Single-Phase Power Meter, 4-Loop CANopen with 60 A CT"
PM-3114-100P-CPS CR is a compact DIN-rail power meter for single-phase energy monitoring over CANopen. It measures true RMS voltage and current and reports active, apparent and reactive power and energy, power factor and frequency, updated every second, so engineers can track consumption on the monitored equipment while it runs.
This variant ships with four clip-on 60 A current transformers, each with a 10 mm inside diameter and a 4 m wire lead. The current input range is 0.05 A to 60 A, and the voltage input accepts 10 to 300 VAC. The meter supports four independent single-phase loops and two Form A power relay outputs, which can drive sirens or lights for alarm signalling.
The unit is suited to generator monitoring, switchgear distribution systems and energy management projects where clip-on CT installation without disconnecting conductors is an advantage. Its W accuracy is better than 0.5% at PF=1.
Applications
- Generator monitoring
- Switchgear distribution systems
- Energy management
| Product type: | Power meter |
|---|---|
| Interface: | CANopen |
| Protocol: | CANopen |
| Relay outputs: | 2 |
| Power input: | +12 ~ 48 VDC |
| Operating temperature: | -20 ~ +70 °C |
| Mounting: | DIN-rail |
| Housing: | Plastic |
Specifications
| AC Power Measurement | |
|---|---|
| Wiring | 1P2W-1CT |
| Loops | 1-phase: 4 |
| Input Voltage | 10 ~ 300 V |
| Input Current | PM-3114-100-CPS: CTØ10 mm (0.05 A ~ 60 A) PM-3114-100P-CPS: CTØ10 mm (0.05 A ~ 60 A) PM-3114-160-CPS: CTØ16 mm (0.1 A ~ 100 A) PM-3114-160P-CPS: CTØ16 mm (0.1 A ~ 100 A) PM-3114-240-CPS: CTØ24 mm (0.15 A ~ 200 A) PM-3114-240P-CPS: CTØ24 mm (0.15 A ~ 200 A) |
| Input Frequency | 50/60 Hz |
| W Accuracy | Better than 0.5% (PF=1) |
| Power Parameter Measurement | True RMS voltage (Vrms), True RMS current (Irms), Active Power (kW), Active Energy (kWh), Apparent Power (kVA), Apparent Energy (kVAh), Reactive Power (kVAR), Reactive Energy (kVARh), Power Factor (PF), Frequency |
| Data Update Rate | 1 Second |
| Relay Output | |
| Channels | 2 |
| Type | Power Relay |
| Contact Rating | Form A: 5 A @ 250 VAC 5 A @ 30 VDC |
| CANopen | |
| Baud Rate | 125 k (default), 250 k, 500 k, 1 M; DIP Switch Selectable |
| Protocol | CANopen |
| Power | |
| Input Range | +12 ~ 48 VDC |
| Consumption | 2W |
| Mechanical | |
| Casing | Plastic |
| Dimensions (mm) | 33 x 127 x 100 (W x L x H) |
| Installation | DIN-Rail Mounting |
| Environment | |
| Operating Temperature | -20 ~ +70 °C |
| Storage Temperature | -25 ~ +80 °C |
| Humidity | 10 ~ 90% RH, Non-condensing |
Specifications as published by the manufacturer. Subject to change.