ET-7250A Ethernet I/O Module with 2-port Switch, 12-ch DI, 6-ch DO
Modbus TCP/UDP Ethernet I/O module with 12 digital inputs usable as 32-bit counters, 6 sink-type digital outputs and a 2-port switch for daisy-chaining.
- Modbus TCP and Modbus UDP support with built-in web server and Web HMI
- 12 digital input channels accepting dry or wet contact, each usable as a 32-bit counter
- 6 isolated open-collector sink-type digital outputs, 500 mA per channel, with short-circuit protection
- 2-port 10/100 Base-TX Ethernet switch with LAN bypass for daisy-chain topology
- Ethernet isolation 1500 VDC and I/O isolation 2500 VDC
- Dual watchdog (module and communication, programmable) and I/O pair connection
€304.00 per piece
| 1-9 pcs | €304.00 | |
|---|---|---|
| 10-30 pcs | €289.00 | −5 % |
| 31+ pcs | €273.00 | −10 % |
Product information "ET-7250A Ethernet I/O Module with 2-port Switch, 12-ch DI, 6-ch DO"
The ET-7250A is an Ethernet I/O module from the ET-7000/ET-7200 series that brings 12 digital inputs and 6 digital outputs onto a Modbus TCP/UDP network. Its built-in web server and Web HMI allow the I/O to be monitored and controlled from a browser, and the module can be read or driven by HMI, SCADA and PLC software over Ethernet.
Each digital input accepts either dry or wet contact signals and can be configured as a 32-bit counter, with a maximum count of 4,294,967,295 and a frequency of 100 Hz. The six outputs are isolated open-collector, sink-type channels rated for 500 mA per channel, with programmable power-on and safe values.
Two RJ-45 switch ports with LAN bypass allow the module to be daisy-chained along the Ethernet line without an external switch. Isolation is rated at 1500 VDC on Ethernet and 2500 VDC on I/O. The unit is powered from +12 ~ +48 VDC and is designed for DIN-rail mounting with an operating range of -25 ~ +75 °C.
Applications
- Building Automation
- Factory Automation
- Machine Automation
- Remote Maintenance
- Remote Diagnosis
- Testing Equipment
| Product type: | Ethernet I/O Module |
|---|---|
| Interface: | Ethernet |
| Protocol: | Modbus TCP, Modbus UDP |
| Digital inputs: | 12 |
| Digital outputs: | 6 |
| Ports: | 2 |
| Isolation: | Ethernet 1500 VDC, I/O 2500 VDC |
| Power input: | +12 ~ +48 VDC |
| Operating temperature: | -25 ~ +75 °C |
| Mounting: | DIN-rail |
Specifications
| Software | |
|---|---|
| Built-in Web Server | Yes |
| CPU Module | |
| Watchdog Timer | Module, Communication (Programmable) |
| Isolation | |
| 2-way Isolation | Ethernet: 1500 VDC I/O: 2500 VDC |
| EMS Protection | |
| EFT (IEC 61000-4-4) | ±4 kV for Power Line |
| ESD (IEC 61000-4-2) | ±4 kV Contact for Each Terminal ±8 kV Air for Random Point |
| LED Indicators | |
| Status | Run, Ethernet, I/O |
| Digital Input/Counter | |
| Channels | 12 |
| Type | Dry Contact Wet Contact |
| Sink/Source (NPN/PNP) | Dry: Source Wet: Sink |
| ON Voltage Level | Dry: Close to GND Wet: 1 VDC (max.) |
| OFF Voltage Level | Dry: Open Wet: +3.5 ~ +50 VDC (max.) |
| Max. Counts | 4,294,967,295 (32-bit) |
| Frequency | 100 Hz |
| Min. Pulse Width | 5 ms |
| Input Impedance | 10 kΩ |
| Overvoltage Protection | +60 VDC |
| Digital Output | |
| Channels | 6 |
| Type | Isolated Open Collector |
| Sink/Source (NPN/PNP) | Sink |
| Load Voltage | +5 ~ +50 VDC |
| Load Current | 500 mA/channel |
| Overvoltage Protection | +60 VDC |
| Overload Protection | 1.3 A |
| Short-circuit Protection | Yes |
| Power on Value | Programmable |
| Safe Value | Programmable |
| Ethernet | |
| Ports | 2 x RJ-45, 10/100 Base-TX, Swtich Ports |
| LAN bypass | Yes |
| Access Control | ID, Password and IP Filter |
| Protocol | Modbus TCP, Modbus UDP |
| Power | |
| Reverse Polarity Protection | Yes |
| Consumption | 2.7 W (max.) |
| Powered from Terminal Block | +12 ~ +48 VDC |
| Mechanical | |
| Dimensions (mm) | 76 x 120 x 42 (W x L x H) |
| Installation | DIN-Rail mounting |
| Environment | |
| Operating Temperature | -25 ~ +75 °C |
| Storage Temperature | -30 ~ +80 °C |
| Humidity | 10 ~ 90% RH, Non-condensing |
Specifications as published by the manufacturer. Subject to change.