CL-223-E Air Quality Data Logger, PM/CO/CO2/RH/Temp, RS-485 & PoE
Data logger module for PM1/PM2.5/PM10, CO, CO2, temperature, humidity and dew point, with RS-485 and Ethernet/PoE connectivity and up to 450,000 time-stamped records.
- Records PM1/PM2.5/PM10, CO, CO2, temperature, humidity and dew point
- NDIR CO2 sensor
- Stores up to 450,000 records with date and time stamps
- RS-485 and Ethernet interfaces with PoE support
- DCON, Modbus RTU, Modbus TCP and MQTT protocol support
- Web-based configuration plus Windows software, iOS and Android apps
€754.00 per piece
| 1-9 pcs | €754.00 | |
|---|---|---|
| 10-30 pcs | €717.00 | −5 % |
| 31+ pcs | €679.00 | −10 % |
Product information "CL-223-E Air Quality Data Logger, PM/CO/CO2/RH/Temp, RS-485 & PoE"
The CL-223-E CR is a wall or ceiling mounted data logger module that records PM1, PM2.5, PM10, CO, CO2, temperature, humidity and dew point. Each reading is stored with date and time stamps, with capacity for up to 450,000 records that can be downloaded for analysis. An NDIR sensor is used for CO2 measurement.
Engineers can integrate the module into existing HMI or SCADA systems through RS-485 or Ethernet, with the Ethernet port also supporting Power over Ethernet. Supported protocols include DCON, Modbus RTU, Modbus TCP and MQTT, and a configuration web interface is provided. A relay output can be used for alarm signalling or to control an indoor air quality device.
The module suits monitoring of food, pharmaceutical and storage environments, as well as building management and indoor car park air quality. Power is supplied from a terminal block at +12 to +48 VDC, or from PoE.
Applications
- Transportation of food or pharmaceuticals
- Food and beverage industry (HACCP)
- Blood stations and pharmacies
- Building and energy management
- Warehouse management
- Museums, archives and galleries
- Indoor or underground car park air quality monitoring
| Product type: | Data logger module |
|---|---|
| Interface: | Ethernet, RS-485 |
| Protocol: | DCON, Modbus RTU, Modbus TCP, MQTT |
| Relay outputs: | 1 |
| Ports: | 2 |
| PoE: | Yes |
| Power input: | +12 ~ +48 VDC |
| Operating temperature: | 0 ~ 50 °C |
| Mounting: | Ceiling/Wall |
| Housing: | Ø 150 x 53 mm |
Specifications
| System | |
|---|---|
| Alarm | PM1/PM2.5/PM10/CO/CO2/RH/Temperature |
| Real Time Clock | Yes |
| Data Logger | Yes, up to 450,000 records |
| Temperature Measurement | |
| Range | -10 ~ +50°C |
| Resolution | 0.1°C |
| Accuracy | ±0.6°C |
| Life Time | 10 years |
| Humidity Measurement | |
| Range | 0 ~ 100% RH, Non-condensing |
| Resolution | 0.1% RH, Non-condensing |
| Accuracy | ±5% RH, Non-condensing |
| Life Time | 10 years |
| Dew Point | |
| Range | Calculated using temperature and relative humidity |
| Resolution | 0.1°C |
| CO Measurement | |
| Range | 0 to 1000 ppm (Electrochemical) |
| Resolution | 1 ppm |
| Accuracy | ±5% of measured value |
| Response Time | 30 seconds |
| Warm-up Time | 5 minutes |
| Life Time | 5 years |
| CO2 Measurement | |
| Range | 0 to 9999 ppm (NDIR) |
| Resolution | 1 ppm |
| Accuracy | ±40 ppm ±3% of measured value |
| Response Time | 120 seconds |
| Warm-up Time | 5 minutes |
| Life Time | 15 years |
| PM1/PM2.5/PM10 Measurement | |
| Range | 0 to 1,000μg/m3 ( Laser Type) |
| Resolution | 1μg/m3 |
| Accuracy | ± 10% of FSR. |
| Response Time | 1 seconds |
| Warm-up Time | 20 seconds |
| Life Time | 5 years, Customer has to replace the filter patch. |
| Particle | |
| Sizes | 0.3μm, 0.5μm, 1μm, 2.5μm, 5μm, 10μm |
| Relay Output | |
| Channels | 1 x Form A, SPST 30 VDC @ 16 A or 250 VAC @ 16 A |
| Ethernet | |
| Ports | 10/100 Base-TX, 8-Pin RJ-45 x1 (Auto-negotiating, Auto-MDI/MDIX, LED indicators) |
| COM Ports | |
| Ports | 1 x RS-485 1 x Ethernet |
| Protocol | DCON and Modbus/RTU (RS-485) Modbus TCP and MQTT (Ethernet) |
| Power | |
| Consumption | Non-PoE: 2.8 W (Max.) PoE: 3.0 W (Max.) |
| Powered from Terminal Block | +12 ~ +48 VDC |
| Mechanical | |
| Dimensions (mm) | Ø 150 x 53 (Ø x H) |
| Installation | Ceiling Mounting/Wall Mounting |
| Ingress Protection Rating | IP20 |
| Environment | |
| Operating Temperature | 0 ~ 50°C |
| Storage Temperature | -30 ~ +75°C |
| Humidity | 10 ~ 90% RH, Non-condensing |
Specifications as published by the manufacturer. Subject to change.