tM-AD5C 5-Channel Isolated Current Input Module, RS-485 Modbus RTU
5-channel differential current input module with programmable ±20 mA, 0 ~ 20 mA and 4 ~ 20 mA ranges, RS-485 DCON and Modbus interface, and 2500 VDC intra-module isolation.
- Five differential current input channels
- Programmable ranges: ±20 mA, 0 ~ 20 mA and 4 ~ 20 mA
- Selectable normal mode (10 Hz, 14-bit, ±0.1%) or fast mode (200 Hz, 12-bit, ±0.5%)
- Single RS-485 port with DCON, Modbus RTU and Modbus ASCII
- 2500 VDC intra-module isolation
- Programmable module and communication watchdogs
143,00 € per piece
| 1–9 pcs | 143,00 € | |
|---|---|---|
| 10–30 pcs | 139,00 € | −3 % |
| 31+ pcs | 136,00 € | −5 % |
Toote teave "tM-AD5C 5-Channel Isolated Current Input Module, RS-485 Modbus RTU"
The tM-AD5C CR is an analog input module for acquiring current signals in RS-485 control and monitoring networks. It provides five differential input channels, and all channels share a programmable range of ±20 mA, 0 ~ 20 mA or 4 ~ 20 mA, so common current loop signals can be measured without changing the hardware.
Sampling can be set to normal mode (10 Hz, 14-bit resolution, ±0.1% accuracy) or fast mode (200 Hz, 12-bit resolution, ±0.5% accuracy), allowing you to balance update rate against resolution and accuracy. The module offers 2500 VDC intra-module isolation and ±4 kV contact ESD protection on each terminal.
Communication uses a single RS-485 port that supports DCON, Modbus RTU and Modbus ASCII at 1200 ~ 115200 bps. Programmable module and communication watchdogs are included, and the unit is powered at 10 ~ 30 VDC from the terminal block with reverse polarity protection. It mounts on a DIN-rail.
Applications
- Industrial Automation
- Industrial Machinery
- Building Automation
- Food and Beverage Systems
- Semiconductor Fabrication
- Control Systems
| Product type: | Analog Input Module |
|---|---|
| Interface: | RS-485 |
| Protocol: | DCON, Modbus ASCII, Modbus RTU |
| Analog inputs: | 5 |
| Ports: | 1 |
| Isolation: | 2500 VDC |
| Power input: | 10 ~ 30 VDC |
| Operating temperature: | -25 ~ +75 °C |
| Mounting: | DIN-rail |
Specifications
| CPU Module | |
|---|---|
| Watchdog Timer | Module, Communication (Programmable) |
| Isolation | |
| Intra-module Isolation | 2500 VDC |
| EMS Protection | |
| EFT (IEC 61000-4-4) | ±4 kV for Power |
| ESD (IEC 61000-4-2) | ±4 kV Contact for Each Terminal ±8 kV Air for Random Point |
| LED Indicators | |
| Status | 1 x Power and Communication |
| Analog Input | |
| Channels | 5 Differential |
| Type | Current |
| Range | ±20 mA, 0 ~ 20 mA, 4 ~ 20 mA |
| Resolution | Normal Mode: 14-bit Fast Mode: 12-bit |
| Accuracy | Normal Mode: ±0.1% Fast Mode: ±0.5% |
| Sampling Rate | Normal Mode: 10 Hz Fast Mode: 200 Hz |
| Input Impedance | 125 Ω |
| COM Ports | |
| Ports | 1 x RS-485 |
| Baud Rate | 1200 ~ 115200 bps |
| Data Format | (N, 8, 1), (N, 8, 2), (O, 8, 1), (E, 8, 1) |
| Protocol | DCON, Modbus RTU, Modbus ASCII |
| Power | |
| Reverse Polarity Protection | Yes |
| Consumption | 1 W max. |
| Powered from Terminal Block | 10 ~ 30 VDC |
| Mechanical | |
| Dimensions (mm) | 52 x 98 x 27 (W x L x H) |
| Installation | DIN-Rail Mounting |
| Environment | |
| Operating Temperature | -25 ~ +75 °C |
| Storage Temperature | -30 ~ +75 °C |
| Humidity | 10 ~ 95% RH, Non-condensing |
Specifications as published by the manufacturer. Subject to change.