PET-7016 PoE I/O Module, 2-ch Strain Gauge Input, 2-ch DI, 2-ch DO
PoE-powered Ethernet I/O module with 2 strain gauge inputs, 2 digital inputs and 2 digital outputs, plus a 0 ~ 10 V excitation output for bridge sensors. Supports Modbus TCP and Modbus UDP.
- Two differential inputs for strain gauge, voltage or current signals, with full-, half- and quarter-bridge wiring
- Individually configurable analog input ranges, from ±15 mV to ±2.5 V and 4 ~ 20 mA
- 0 ~ 10 V excitation voltage output rated at 60 mA maximum load current
- Two wet-contact digital inputs with 32-bit counters, 100 Hz frequency and 5 ms minimum pulse width
- Two isolated open-collector digital outputs, 700 mA per channel, with short-circuit protection and configurable alarm function
- Modbus TCP and Modbus UDP over 10/100 Base-TX Ethernet, with built-in web server and Web HMI
€399.00 per piece
| 1-9 pcs | €399.00 | |
|---|---|---|
| 10-30 pcs | €379.00 | −5 % |
| 31+ pcs | €359.00 | −10 % |
Product information "PET-7016 PoE I/O Module, 2-ch Strain Gauge Input, 2-ch DI, 2-ch DO"
The PET-7016 brings bridge sensor measurement to an Ethernet I/O node. It combines two differential strain gauge, voltage and current inputs with a single 0 ~ 10 V excitation output, so a bridge or load cell can be read and excited from one module. Each analog input range can be set individually, and full-bridge, half-bridge and quarter-bridge wiring are supported.
Beyond the analog front end, the module includes two wet-contact digital inputs with counter functions and two isolated open-collector digital outputs. The digital outputs can also be configured as alarm outputs. Long-distance strain gauge measurement is supported, with compensation for voltage loss over long cable runs.
Communication is over a single 10/100 Base-TX RJ-45 port with Modbus TCP and Modbus UDP, and the module can be powered over PoE (IEEE 802.3af, Class 1) or from a +12 ~ +48 VDC terminal block. A built-in web server and Web HMI, along with ID, password and IP filter access control, support configuration and remote monitoring.
Applications
- Building Automation
- Factory Automation
- Machine Automation
- Remote Maintenance
- Remote Diagnosis
- Testing Equipment
| Product type: | Ethernet I/O Module |
|---|---|
| Interface: | Ethernet |
| Protocol: | Modbus TCP, Modbus UDP |
| Digital inputs: | 2 |
| Digital outputs: | 2 |
| Analog inputs: | 2 |
| Ports: | 1 |
| PoE: | Yes |
| Isolation: | 2500 VDC |
| Power input: | PoE (IEEE 802.3af Class 1), +12 ~ +48 VDC |
| Operating temperature: | -25 ~ +75 °C |
| Mounting: | DIN-rail |
Specifications
| Software | |
|---|---|
| Built-in Web Server | Yes |
| CPU Module | |
| Watchdog Timer | Module, Communication (Programmable) |
| Isolation | |
| 2-way Isolation | I/O: 2500 VDC |
| EMS Protection | |
| EFT (IEC 61000-4-4) | ±4 kV for Power Line |
| ESD (IEC 61000-4-2) | ±4 kV Contact for Each Terminal ±8 kV Air for Random Point |
| LED Indicators | |
| Status | Run, Ethernet, PoE |
| Digital Input/Counter | |
| Channels | 2 |
| Type | Wet Contact |
| Sink/Source (NPN/PNP) | Sink/Source |
| ON Voltage Level | +3.5 ~ +50 VDC |
| OFF Voltage Level | +1 VDC (max.) |
| Max. Counts | 4,294,967,295 (32-bit) |
| Frequency | 100 Hz |
| Min. Pulse Width | 5 ms |
| Overvoltage Protection | +70 VDC |
| Digital Output | |
| Channels | 2 |
| Type | Isolated Open Collector |
| Sink/Source (NPN/PNP) | Sink |
| Load Voltage | +5 ~ +50 VDC |
| Load Current | 700 mA/channel |
| Overvoltage Protection | +60 VDC |
| Overload Protection | 1.4 A |
| Short-circuit Protection | Yes |
| Power on Value | Programmable |
| Safe Value | Programmable |
| Strain Gauge, Load Cell Input | |
| Channels | 2 (Differential) |
| Type | Strain Gauge, Voltage, Current |
| Range | ±15 mV, ±50 mV, ±100 mV, ±500 mV, ±1 V, ±2.5 V ±20mA, 10 ~ 20 mA, 4 ~ 20 mA |
| Wiring | Full-Bridge, Half-Bridge, Quarter-Bridge |
| Accuracy | ±0.05% |
| Resolution | 16-bit |
| Sampling Rate | 10 Hz (total channels) |
| Impedance | Voltage Input: >400 kΩ, Current Input: 125 Ω |
| Individual Channel Configuration | Yes |
| Overvoltage Protection | +30 VDC |
| Excitation Voltage Output | |
| Channels | 1 |
| Range | 0 ~ 10 V |
| Accuracy | ±0.05% of FSR |
| Max. Load Current | 60 mA |
| Drift | ±50 ppm/°C |
| Power on Value | Programmable |
| Ethernet | |
| Ports | 1 x RJ-45, 10/100 Base-TX |
| PoE | Yes |
| Access Control | ID, Password and IP Filter |
| Protocol | Modbus TCP, Modbus UDP |
| Power | |
| Reverse Polarity Protection | Yes |
| Consumption | 3.2 W (max.) |
| Powered from PoE | IEEE 802.3af, Class1 |
| Powered from Terminal Block | +12 ~ +48 VDC |
| Mechanical | |
| Dimensions (mm) | 72 x 123 x 35 (W x L x H) |
| Installation | DIN-Rail mounting |
| Environment | |
| Operating Temperature | -25 ~ +75 °C |
| Storage Temperature | -30 ~ +80 °C |
| Humidity | 10 ~ 90% RH, Non-condensing |
Specifications as published by the manufacturer. Subject to change.
Downloads
Login