tM-AD2 CR is a DIN-rail analog input module for RS-485 remote I/O networks. It has two single-ended inputs that accept voltage and current signals, and each input can be set to one of seven ranges, from 0 ~ 500 mV up to 4 ~ 20 mA. Individual channel configuration and open wire detection help with commissioning and fault finding.

Engineers choose the tM-AD2 CR when signals need to be read reliably in electrically noisy or exposed environments. It offers 2500 VDC intra-module isolation, 120 VDC overvoltage protection, 4 kV ESD protection and reverse polarity protection on the power input. The module runs from 10 ~ 30 VDC and draws 0.7 W max.

The sampling rate is adjustable. Normal mode gives 14-bit resolution and ±0.1% accuracy at 10 Hz, while fast mode gives 12-bit resolution and ±0.5% accuracy at 200 Hz. The module communicates over one RS-485 port using DCON, Modbus RTU or Modbus ASCII, and a dual watchdog covers the module and communication.

Applications

  • Industrial automation
  • Industrial machinery
  • Building automation
  • Food and beverage systems
  • Semiconductor fabrication
  • Control systems
Product type: Analog Input Module
Interface: RS-485
Protocol: DCON, Modbus ASCII, Modbus RTU
Analog inputs: 2
Ports: 1
Isolation: 2500 VDC
Power input: 10 ~ 30 VDC
Operating temperature: -25 ~ +75 °C
Mounting: DIN-rail

Specifications

CPU Module
Watchdog TimerModule, Communication (Programmable)
Isolation
Intra-module Isolation2500 VDC
EMS Protection
EFT (IEC 61000-4-4)±4 kV for Power
ESD (IEC 61000-4-2)±4 kV Contact for Each Terminal
±8 kV Air for Random Point
LED Indicators
Status1 x Power and Communication
Analog Input
Channels2 Single-ended
TypeVoltage,
Current
Range0 ~ 500 mV, 0 ~ 1 V, 0 ~ 2.5 V, 0 ~ 5 V, 0 ~ 10 V, 0 ~ 20 mA, 4 ~ 20 mA
ResolutionNormal Mode: 14-bit
Fast Mode: 12-bit
AccuracyNormal Mode: ±0.1%
Fast Mode: ±0.5%
Sampling RateNormal Mode: 10 Hz
Fast Mode: 200 Hz
Input ImpedanceVoltage: 10 MΩ
Current: 125 Ω
Overvoltage Protection120 VDC
Overcurrent Protection50 mA at 110 VDC
Individual Channel ConfigurationYes
Open Wire DetectionYes
COM Ports
Ports1 x RS-485
Baud Rate1200 ~ 115200 bps
Data Format(N, 8, 1), (N, 8, 2), (O, 8, 1), (E, 8, 1)
ProtocolDCON, Modbus RTU, Modbus ASCII
Power
Reverse Polarity ProtectionYes
Consumption0.7 W max.
Powered from Terminal Block10 ~ 30 VDC
Mechanical
Dimensions (mm)52 x 98 x 27 (W x L x H)
InstallationDIN-Rail Mounting
Environment
Operating Temperature-25 ~ +75 °C
Storage Temperature-30 ~ +75 °C
Humidity10 ~ 95% RH, Non-condensing

Specifications as published by the manufacturer. Subject to change.