Skip to main content Skip to search Skip to main navigation

iWSN-9603-RCT2000P-ME-IP33 Wireless 3-Phase Power Meter, 2000 A Rogowski CT

Product information "iWSN-9603-RCT2000P-ME-IP33 Wireless 3-Phase Power Meter, 2000 A Rogowski CT"

iWSN-9603-RCT2000P-ME-IP33 is a wireless 3-phase power meter for measuring energy use on equipment fed from the same AC source. It takes one 3-phase voltage input and two 3-phase current loops, using six Rogowski current transformers rated up to 2000 A with an 105 mm inside diameter and 4 m wire leads. Readings are sent over 433 MHz radio, so the meter suits distributed or quickly commissioned installations where running extra power cabling is impractical.

This ordering code is the highest-current option in the iWSN-9603 series. The -RCT500P and -RCT1000P variants use 500 A and 1000 A Rogowski CTs with 55 mm and 80 mm inside diameters respectively. The Wh accuracy figure of better than 2% at PF=1 applies only when the input current exceeds 200 A for this model, so the lower end of the range is outside that specified condition.

  • Measures 3P4W, 3P3W, 3P3W 2CT, 1P3W and 1P2W wiring with bi-directional kWh measurement
  • True RMS voltage and current, active power, active energy, power factor and frequency
  • Built-in RTC timestamps each measurement, with a 3-minute history cache for data supplement
  • Self-powered from the measured voltage input, rated 100 - 480 VAC (58 - 277 VAC single phase)
  • 433 MHz radio with up to 64 wireless sub-networks, and a built-in omni-directional antenna
  • IP33 housing and connector cover for installations outside a panel box

The meter is configured through DIP switches and is intended for wall mounting. Typical uses include machine and process power efficiency work, power information management, carbon emission calculation, predictive maintenance and analysis of power consumption data.

Applications

  • Machine and process power efficiency improvement
  • Power information administration
  • Calculation of carbon emission
  • Predictive maintenance
  • Big data analysis of power consumption
Product type: Power meter
Interface: 433 MHz wireless
Power input: 100 - 480 VAC
Operating temperature: -30 ~ +50 °C
Mounting: Wall-mount
Housing: IP33

Specifications

EMS Protection
EFT (IEC 61000-4-4)+/- 500 V
ESD (IEC 61000-4-2)+/- 4 kV Contact
LED Indicators
Status1 x Power
1 x Tx
1 x Error
AC Power Measurement
Wiring3P4W-3CT, 3P3W-2CT, 3P3W-3CT, 1P2W-1CT, 1P3W-2CT
Loops4(Single Phase)/ 2(Three Phase)
Input Voltage100 - 480 VAC (58 - 277 VAC single phase)
Input CurrentiWSN-9603-RCT500P-ME-IP33: CTØ55 mm (5A ~ 500 A)
iWSN-9603-RCT1000P-ME-IP33: CTØ80 mm (5 A ~ 1000 A)
iWSN-9603-RCT2000P-ME-IP33: CTØ105 mm (5 A ~ 2000 A)
Input Frequency50/60 Hz
Wh AccuracyBetter than 2% (PF=1)
Condition:
Input current > 50A; (For -500P, -1000P)
Input current > 200A; (For -2000P)
Power Parameter MeasurementTrue RMS voltage (Vrms), True RMS current (Irms), Active Power (kW), Active Energy (kWh), Power Factor (PF), Frequency
Data Update Rate1, 10, 30, or 60 Seconds
RF
Channels0 ~ 15
Group ID0 ~ 3
Radio Frequency433.1000 ~ 434.6000 MHz
Transmission Power9±1dBm (PA Off) / 18±1dBm (PA On)
Transmission Distance (LoS)100 m
Node ID1 ~ 31
Working Duty1, 10, 30, or 60 Seconds
Antenna
TypeBuilt-in Omni-directional antenna
Power
Consumption3W
Input TypeThree phase 100 - 480 VAC
(58 - 277 VAC single phase)
Mechanical
Dimensions (mm)85 x 184 x 47 (W x L x H)
InstallationWall-mount
Ingress Protection RatingIP33
Environment
Operating Temperature-30 °C ~ +50 °C
Storage Temperature-40 °C ~ +55 °C
Humidity10 ~ 90% RH, Non-condensing

Specifications as published by the manufacturer. Subject to change.

0 of 0 reviews

Average rating of 0 out of 5 stars

Leave a review!

Share your experiences with other customers.