iWSN-9603-RCT2000P-ME-IP33 Wireless 3-Phase Power Meter, 2000 A Rogowski CT
Wireless 3-phase power meter with six 2000 A Rogowski current transformers (105 mm inside diameter) for energy monitoring. Powered from the measured voltage cable, with no separate supply wiring.
- Six 2000 A Rogowski CTs with 105 mm inside diameter and 4 m leads, for high-current 3-phase and single-phase loads
- Wiring options include 3P4W, 3P3W, 3P3W 2CT, 1P3W and 1P2W, with bi-directional kWh measurement
- Self-powered from the measured voltage cable, reducing installation time and cost
- 433 MHz wireless with up to 64 sub-networks; rated transmission distance of 100 m line of sight
- Built-in RTC timestamps each measurement; 3-minute history cache supports data supplementation
- True RMS voltage and current with power, energy, power factor and frequency measurement
€2,249.00 per piece
| 1–9 pcs | €2,249.00 | |
|---|---|---|
| 10–30 pcs | €2,182.00 | −3 % |
| 31+ pcs | €2,137.00 | −5 % |
Product information "iWSN-9603-RCT2000P-ME-IP33 Wireless 3-Phase Power Meter, 2000 A Rogowski CT"
iWSN-9603-RCT2000P-ME-IP33 is a wireless 3-phase power meter for measuring energy use on equipment fed from the same AC source. It takes one 3-phase voltage input and two 3-phase current loops, using six Rogowski current transformers rated up to 2000 A with an 105 mm inside diameter and 4 m wire leads. Readings are sent over 433 MHz radio, so the meter suits distributed or quickly commissioned installations where running extra power cabling is impractical.
This ordering code is the highest-current option in the iWSN-9603 series. The -RCT500P and -RCT1000P variants use 500 A and 1000 A Rogowski CTs with 55 mm and 80 mm inside diameters respectively. The Wh accuracy figure of better than 2% at PF=1 applies only when the input current exceeds 200 A for this model, so the lower end of the range is outside that specified condition.
- Measures 3P4W, 3P3W, 3P3W 2CT, 1P3W and 1P2W wiring with bi-directional kWh measurement
- True RMS voltage and current, active power, active energy, power factor and frequency
- Built-in RTC timestamps each measurement, with a 3-minute history cache for data supplement
- Self-powered from the measured voltage input, rated 100 - 480 VAC (58 - 277 VAC single phase)
- 433 MHz radio with up to 64 wireless sub-networks, and a built-in omni-directional antenna
- IP33 housing and connector cover for installations outside a panel box
The meter is configured through DIP switches and is intended for wall mounting. Typical uses include machine and process power efficiency work, power information management, carbon emission calculation, predictive maintenance and analysis of power consumption data.
Applications
- Machine and process power efficiency improvement
- Power information administration
- Calculation of carbon emission
- Predictive maintenance
- Big data analysis of power consumption
| Product type: | Power meter |
|---|---|
| Interface: | 433 MHz wireless |
| Power input: | 100 - 480 VAC |
| Operating temperature: | -30 ~ +50 °C |
| Mounting: | Wall-mount |
| Housing: | IP33 |
Specifications
| EMS Protection | |
|---|---|
| EFT (IEC 61000-4-4) | +/- 500 V |
| ESD (IEC 61000-4-2) | +/- 4 kV Contact |
| LED Indicators | |
| Status | 1 x Power 1 x Tx 1 x Error |
| AC Power Measurement | |
| Wiring | 3P4W-3CT, 3P3W-2CT, 3P3W-3CT, 1P2W-1CT, 1P3W-2CT |
| Loops | 4(Single Phase)/ 2(Three Phase) |
| Input Voltage | 100 - 480 VAC (58 - 277 VAC single phase) |
| Input Current | iWSN-9603-RCT500P-ME-IP33: CTØ55 mm (5A ~ 500 A) iWSN-9603-RCT1000P-ME-IP33: CTØ80 mm (5 A ~ 1000 A) iWSN-9603-RCT2000P-ME-IP33: CTØ105 mm (5 A ~ 2000 A) |
| Input Frequency | 50/60 Hz |
| Wh Accuracy | Better than 2% (PF=1) Condition: Input current > 50A; (For -500P, -1000P) Input current > 200A; (For -2000P) |
| Power Parameter Measurement | True RMS voltage (Vrms), True RMS current (Irms), Active Power (kW), Active Energy (kWh), Power Factor (PF), Frequency |
| Data Update Rate | 1, 10, 30, or 60 Seconds |
| RF | |
| Channels | 0 ~ 15 |
| Group ID | 0 ~ 3 |
| Radio Frequency | 433.1000 ~ 434.6000 MHz |
| Transmission Power | 9±1dBm (PA Off) / 18±1dBm (PA On) |
| Transmission Distance (LoS) | 100 m |
| Node ID | 1 ~ 31 |
| Working Duty | 1, 10, 30, or 60 Seconds |
| Antenna | |
| Type | Built-in Omni-directional antenna |
| Power | |
| Consumption | 3W |
| Input Type | Three phase 100 - 480 VAC (58 - 277 VAC single phase) |
| Mechanical | |
| Dimensions (mm) | 85 x 184 x 47 (W x L x H) |
| Installation | Wall-mount |
| Ingress Protection Rating | IP33 |
| Environment | |
| Operating Temperature | -30 °C ~ +50 °C |
| Storage Temperature | -40 °C ~ +55 °C |
| Humidity | 10 ~ 90% RH, Non-condensing |
Specifications as published by the manufacturer. Subject to change.
Login