Skip to main content Skip to search Skip to main navigation

SG-3013-G RTD Input Signal Conditioner with Voltage/Current Output

Product information "SG-3013-G RTD Input Signal Conditioner with Voltage/Current Output"

The SG-3013-G CR conditions a single RTD sensor signal and delivers it as a standard voltage or current output for control and monitoring equipment. It accepts Pt100, Ni 120 and Pt1000 sensors, and internal configuration switches let you adjust the input and output ranges without changing the hardware.

Isolation and accuracy: Input, output and power are separated by 1000 VDC three-way isolation, and the module holds an accuracy of ±0.1% of full range with a 100 ms response time. It is rated for operation from -25 °C to 75 °C, so it suits installations with a wide temperature range.

Installation: The module mounts on a standard DIN rail in a 25 mm x 114 mm x 70 mm housing. Reverse polarity protection is fitted on the supply input, and the ordering code is listed as RoHS compliant.

Product type: Signal conditioner
Isolation: 1000 VDC
Power input: +10 ~ +30 VDC
Operating temperature: -25 ~ +75 °C
Mounting: DIN-rail

Specifications

Isolation
Three-way Isolation1000 VDC
Analog Input
Channels1
TypePt100 α=0.00385 / Pt100 α=0.003916 / Ni 120 / Pt1000 α=0.00385
Accuracy±0.1% of full range
Response Time100 ms
Analog Output
Channels1
RangeVoltage: 0 ~ 5 VDC, 0 ~ 10 VDC
Current: 0 ~ 20 mA, 4 ~ 20 mA
Current Load Resistance0 ~ 500 Ω (Source)
Power
Reverse Polarity ProtectionYes
Input Range+10 ~ +30 VDC
Consumption1.2 W
Mechanical
Dimensions (mm)25 mm x 114 mm x 70 mm (W x L x H)
Environment
Operating Temperature-25 °C ~ 75 °C
Storage Temperature30 °C ~ 75 °C
Humidity5 ~ 95%, non-condensing

Specifications as published by the manufacturer. Subject to change.

0 of 0 reviews

Average rating of 0 out of 5 stars

Leave a review!