PET-7226 PoE Ethernet I/O Module, 6-ch AI, 2-ch AO, 2-ch DI, 2-ch DO
PoE Modbus TCP/UDP I/O module with 6 analogue inputs, 2 analogue outputs, 2 digital inputs and 2 digital outputs, plus a 2-port switch with LAN bypass for daisy-chaining.
- Six differential analogue inputs with voltage and current ranges selectable by jumper, including 4 ~ 20 mA with open wire detection
- 16-bit analogue input resolution with normal mode accuracy of ±0.1%, sampling at 10 Hz normal or 50 Hz fast mode across all channels
- Two 12-bit analogue outputs with programmable power-on and safe values
- Two digital inputs with 32-bit counters, 100 Hz frequency and 5 ms minimum pulse width
- Two isolated open-collector digital outputs, 700 mA per channel, with short-circuit protection
- Two-port 10/100 Base-TX switch with LAN bypass for daisy-chain topology
€448.00 per piece
| 1-9 pcs | €448.00 | |
|---|---|---|
| 10-30 pcs | €426.00 | −5 % |
| 31+ pcs | €404.00 | −10 % |
Product information "PET-7226 PoE Ethernet I/O Module, 6-ch AI, 2-ch AO, 2-ch DI, 2-ch DO"
The PET-7226 CR is a multifunction Ethernet I/O module that combines six analogue inputs, two analogue outputs, two digital inputs with counter capability and two digital outputs in one DIN-rail unit. It is powered over Ethernet or from a terminal block, so a single network cable can serve both communication and power in a distributed I/O design.
Each analogue input can be set to a suitable voltage or current range, and each analogue input and output can be switched between voltage and current using its jumper position. Every analogue input is protected against overvoltage up to 240 Vrms, which helps when the module is connected to field wiring of varying quality.
The built-in two-port switch with LAN bypass allows the module to be daisy-chained along a network line. Modbus TCP and Modbus UDP are supported, and the built-in web server provides a web HMI for configuration and monitoring.
Applications
- Building automation
- Factory automation
- Machine automation
- Remote maintenance
- Remote diagnosis
- Testing equipment
| Product type: | Ethernet I/O Module |
|---|---|
| Interface: | Ethernet |
| Protocol: | Modbus TCP, Modbus UDP |
| Digital inputs: | 2 |
| Digital outputs: | 2 |
| Analog inputs: | 6 |
| Analog outputs: | 2 |
| Ports: | 2 |
| PoE: | Yes |
| Isolation: | 2500 VDC |
| Power input: | +12 ~ +48 VDC |
| Operating temperature: | -25 ~ +75 °C |
| Mounting: | DIN-rail |
Specifications
| Software | |
|---|---|
| Built-in Web Server | Yes |
| CPU Module | |
| Watchdog Timer | Module, Communication (Programmable) |
| Isolation | |
| 2-way Isolation | I/O: 2500 VDC |
| EMS Protection | |
| EFT (IEC 61000-4-4) | ±2 kV for Power Line |
| ESD (IEC 61000-4-2) | ±4 kV Contact for Each Terminal ±8 kV Air for Random Point |
| Surge (IEC 61000-4-5) | ±2 kV for Power Line |
| LED Indicators | |
| Status | Run, Ethernet, I/O, PoE |
| Analog Input | |
| Channels | 6 (Differential) |
| Type | Voltage Current |
| Range | ±500 mV, ±1V, ±5 V, ±10 V 0 ~ 20 mA, ±20 mA, 4 ~ 20 mA (Jumper Selectable) |
| Resolution | 16-bit |
| Accuracy | Normal Mode: ±0.1% Fast Mode: ±0.5% or better |
| Sampling Rate | Normal Mode: 10 Hz (total channels) Fast Mode: 50 Hz (total channels) |
| Input Impedance | Voltage: 2 MΩ Current: 125 Ω |
| Common Voltage Protection | ±200 VDC |
| Overvoltage Protection | 240 Vrms |
| Overcurrent Protection | 50 mA at 110 VDC (max.) |
| Individual Channel Configuration | Yes |
| Open Wire Detection | For 4 ~ 20 mA only |
| Isolation | ±400 VDC, Virtual Channel to Channel Isolation |
| Analog Output | |
| Channels | 2 |
| Type | Voltage Current |
| Range | +0 ~ +5 VDC, ±5 VDC, +0 ~ +10 VDC, ±10 VDC 0 ~ 20 mA, 4 ~ 20 mA (Jumper Selectable) |
| Resolution | 12-bit |
| Accuracy | ±0.1% of FSR |
| Open Wire Detection | For 4 ~ 20 mA only |
| Voltage Output Capability | 10 V @ 20 mA |
| Current Load Resistance | 500 Ω |
| Individual Channel Configuration | Yes |
| Power-on Value | Programmable |
| Safe Value | Programmable |
| Digital Input/Counter | |
| Channels | 2 |
| Type | Dry Contact Wet Contact |
| ON Voltage Level | Dry: Close to GND Wet: +1 VDC (max.) |
| OFF Voltage Level | Dry: Open Wet: +3.5 ~ +30 VDC |
| Max. Counts | 4,294,967,295 (32-bit) |
| Frequency | 100 Hz |
| Min. Pulse Width | 5 ms |
| Effective Distance | 500m (max.) |
| Overvoltage Protection | +30 VDC |
| Digital Output | |
| Channels | 2 |
| Type | Isolated Open Collector |
| Sink/Source (NPN/PNP) | Sink |
| Load Voltage | +5 ~ +50 VDC |
| Load Current | 700 mA/channel |
| Overvoltage Protection | +60 VDC |
| Overload Protection | 1.4 A |
| Short-circuit Protection | Yes |
| Power on Value | Programmable |
| Safe Value | Programmable |
| Ethernet | |
| Ports | 2 x RJ-45, 10/100 Base-TX, Swtich Ports |
| PoE | Yes |
| LAN bypass | Yes |
| Access Control | ID, Password and IP Filter |
| Protocol | Modbus TCP, Modbus UDP |
| Power | |
| Reverse Polarity Protection | Yes |
| Consumption | 5.2 W (max.) |
| Powered from PoE | IEEE 802.3af, Class1 |
| Powered from Terminal Block | +12 ~ +48 VDC |
| Mechanical | |
| Dimensions (mm) | 76 x 120 x 42 (W x L x H) |
| Installation | DIN-Rail mounting |
| Environment | |
| Operating Temperature | -25 ~ +75 °C |
| Storage Temperature | -30 ~ +80 °C |
| Humidity | 10 ~ 90% RH, Non-condensing |
Specifications as published by the manufacturer. Subject to change.