PET-7217-10 PoE Ethernet I/O Module, 10/20-ch Analog Input
PoE-powered Ethernet I/O module with a 2-port switch and 10/20-channel analog inputs, supporting Modbus TCP and Modbus UDP for network-based monitoring.
- 10 differential or 20 single-ended analog inputs, software selectable
- Individual channel range configuration; voltage or current input set by jumper
- 16-bit resolution with normal (10 Hz) and fast (50 Hz) sampling modes
- PoE (IEEE 802.3af, Class 1) or +12 ~ +48 VDC terminal block power
- 2-port 10/100 Base-TX switch with LAN bypass for daisy-chain topology
- Modbus TCP and Modbus UDP support with built-in web server and web HMI
€415.00 per piece
| 1-9 pcs | €415.00 | |
|---|---|---|
| 10-30 pcs | €395.00 | −5 % |
| 31+ pcs | €374.00 | −10 % |
Product information "PET-7217-10 PoE Ethernet I/O Module, 10/20-ch Analog Input"
PET-7217-10 CR is a PoE-powered Ethernet I/O module that brings analog measurement onto a Modbus network. It accepts either 10 differential or 20 single-ended analog inputs, selectable in software, and each channel can be configured with its own input range. Voltage or current input is chosen per channel by jumper position.
The module has a built-in 2-port 10/100 Base-TX switch with LAN bypass, so units can be daisy-chained along a line without a separate switch. It is equipped with a built-in web server and web HMI for configuration, and supports both Modbus TCP and Modbus UDP. Access control uses ID, password and IP filtering, and dual watchdogs cover the module and communication.
Two sampling modes are available: normal mode at 10 Hz and fast mode at 50 Hz across all channels. The module can be powered over PoE (IEEE 802.3af, Class 1) or from a +12 ~ +48 VDC terminal block, and mounts on a DIN rail.
Applications
- Building Automation
- Factory Automation
- Machine Automation
- Remote Maintenance
- Remote Diagnosis
- Testing Equipment
| Product type: | Ethernet I/O Module |
|---|---|
| Interface: | Ethernet |
| Protocol: | Modbus TCP, Modbus UDP |
| Analog inputs: | 10 differential / 20 single-ended |
| Ports: | 2 |
| PoE: | Yes |
| Isolation: | 2500 VDC |
| Power input: | PoE (IEEE 802.3af), +12 ~ +48 VDC |
| Operating temperature: | -25 ~ +75 °C |
| Mounting: | DIN-rail |
Specifications
| Software | |
|---|---|
| Built-in Web Server | Yes |
| CPU Module | |
| Watchdog Timer | Module, Communication (Programmable) |
| Isolation | |
| 2-way Isolation | I/O: 2500 VDC |
| EMS Protection | |
| EFT (IEC 61000-4-4) | ±2 kV for Power Line |
| ESD (IEC 61000-4-2) | ±4 kV Contact for Each Terminal ±8 kV Air for Random Point |
| Surge (IEC 61000-4-5) | ±2 kV for Power Line |
| LED Indicators | |
| Status | Run, Ethernet, I/O, PoE |
| Analog Input | |
| Channels | 10 differential or 20 single-ended (Note1), software selectable |
| Type | Voltage Current |
| Range | ±150 mV, ±500 mV, ±1 V, ±5 V, ±10 V ±20 mA, 0 ~ 20 mA, 4 ~ 20 mA (Jumper Selectable) |
| Resolution | 16-bit |
| Accuracy | Normal Mode: ±0.1% Fast Mode: ±0.5% or better |
| Sampling Rate | Normal Mode: 10 Hz (total channels) Fast Mode: 50 Hz (total channels) |
| Input Impedance | Voltage: 2 MΩ (Differential), 1 MΩ (Single-ended) Current: 125 Ω |
| Common Voltage Protection | ±200 VDC |
| Overvoltage Protection | Differential: 240 Vrms Single-ended: 150 Vrms |
| Overcurrent Protection | 50 mA at 110 VDC (max.) |
| Individual Channel Configuration | Yes |
| Open Wire Detection | For 4 ~ 20 mA only |
| Isolation | ±400 VDC, Virtual Channel to Channel Isolation |
| Ethernet | |
| Ports | 2 x RJ-45, 10/100 Base-TX, Swtich Ports |
| PoE | Yes |
| LAN bypass | Yes |
| Access Control | ID, Password and IP Filter |
| Protocol | Modbus TCP, Modbus UDP |
| Power | |
| Reverse Polarity Protection | Yes |
| Consumption | 3.8 W (max.) |
| Powered from PoE | IEEE 802.3af, Class1 |
| Powered from Terminal Block | +12 ~ +48 VDC |
| Mechanical | |
| Dimensions (mm) | 76 x 120 x 42 (W x L x H) |
| Installation | DIN-Rail mounting |
| Environment | |
| Operating Temperature | -25 ~ +75 °C |
| Storage Temperature | -30 ~ +80 °C |
| Humidity | 10 ~ 90% RH, Non-condensing |
Specifications as published by the manufacturer. Subject to change.