CL-201-E CO, Temperature, Humidity & Dew Point Data Logger Module, PoE
CL-201-E CR logs CO, temperature, humidity and dew point with date and time stamps, storing up to 450,000 records, with RS-485 and Ethernet PoE connectivity.
- Measures CO (0 to 1000 ppm, electrochemical), temperature, humidity and dew point
- Stores up to 450,000 time-stamped records with a real-time clock
- Supports DCON, Modbus RTU, Modbus TCP and MQTT protocols
- RS-485 and 10/100 Base-TX Ethernet interfaces with PoE, plus a +12 ~ +48 VDC terminal block supply
- 1 x Form A (SPST) relay output rated 16 A for alarm or IAQ device control
- Temperature range -10 ~ +50°C, humidity 0 ~ 100% RH non-condensing
€312.00 per piece
| 1–9 pcs | €312.00 | |
|---|---|---|
| 10–30 pcs | €302.00 | −3 % |
| 31+ pcs | €296.00 | −5 % |
Product information "CL-201-E CO, Temperature, Humidity & Dew Point Data Logger Module, PoE"
CL-201-E CR is a CO, temperature, humidity and dew point data logger module for monitoring indoor air quality and environmental conditions. Each reading is time-stamped and stored on the module, which holds up to 450,000 records for later download.
The module reports over RS-485 and Ethernet with PoE, and supports DCON, Modbus RTU, Modbus TCP and MQTT. This makes it straightforward to pass readings into an existing HMI, SCADA or IoT platform in distributed control systems. A single Form A relay output can be used for alarm signalling or for controlling IAQ equipment.
Logged data can be exported to CSV from the iAir Utility, which also allows the modules to be configured, grouped and monitored in real time. The unit is specified for 0 ~ 50°C operation and is intended for ceiling or wall mounting.
Applications
- Transportation of food or pharmaceuticals
- Food and beverage industry (HACCP)
- Blood stations and pharmacies
- Building and energy management
- Warehouse management
- Museums, archives and galleries
- Indoor or underground car park air quality monitoring
| Product type: | Data logger module |
|---|---|
| Interface: | Ethernet, RS-485 |
| Protocol: | DCON, Modbus RTU, Modbus TCP, MQTT |
| Relay outputs: | 1 x Form A (SPST) |
| Ports: | 2 |
| PoE: | Yes |
| Power input: | +12 ~ +48 VDC |
| Operating temperature: | 0 ~ 50°C |
| Mounting: | Ceiling/Wall |
Specifications
| System | |
|---|---|
| Alarm | CO/RH/Temperature |
| Real Time Clock | Yes |
| Data Logger | Yes, up to 450,000 records |
| Temperature Measurement | |
| Range | -10 ~ +50°C |
| Resolution | 0.1°C |
| Accuracy | ±0.6°C |
| Humidity Measurement | |
| Range | 0 ~ 100% RH, Non-condensing |
| Resolution | 0.1% RH, Non-condensing |
| Accuracy | ±5% RH, Non-condensing |
| CO Measurement | |
| Range | 0 to 1000 ppm (Electrochemical) |
| Resolution | 1 ppm |
| Accuracy | ±5% of measured value |
| Response Time | 30 seconds |
| Warm-up Time | 5 minutes |
| Relay Output | |
| Channels | 1 x Form A, SPST 30 VDC @ 16 A or 250 VAC @ 16 A |
| Ethernet | |
| Ports | 10/100 Base-TX, 8-Pin RJ-45 x1 (Auto-negotiating, Auto-MDI/MDIX, LED indicators) |
| COM Ports | |
| Ports | 1 x RS-485 1 x Ethernet |
| Protocol | DCON and Modbus/RTU (RS-485) Modbus TCP and MQTT (Ethernet) |
| Power | |
| Consumption | Non-PoE: 1.5 W (Max.) PoE: 1.6 W (Max.) |
| Powered from Terminal Block | +12 ~ +48 VDC |
| Mechanical | |
| Dimensions (mm) | Ø 150 x 53 (Ø x H) |
| Installation | Ceiling Mounting/Wall Mounting |
| Ingress Protection Rating | IP20 |
| Environment | |
| Operating Temperature | 0 ~ 50°C |
| Storage Temperature | -30 ~ +75°C |
| Humidity | 10 ~ 90% RH, Non-condensing |
Specifications as published by the manufacturer. Subject to change.