ET-2254 Ethernet I/O Module, 16-ch Universal DIO with 2-port Switch
16-channel universal DIO Ethernet I/O module with a built-in 2-port switch for daisy-chain wiring, supporting Modbus TCP/UDP, MQTT and SNMP V2c.
- 16 programmable universal channels, each set as a digital input or digital output
- Built-in 2-port 10/100 Base-Tx switch with LAN bypass for daisy-chain wiring
- Modbus TCP/UDP, MQTT and SNMP V2c protocol support
- I/O Pair Connection in Push and Pull modes between modules over Ethernet
- Digital outputs rated at 100 mA per channel, +5 ~ +30 VDC load voltage
- 3000 VDC I/O isolation with EFT, ESD and surge protection
187,00 € per piece
| 1–9 pcs | 187,00 € | |
|---|---|---|
| 10–30 pcs | 182,00 € | −3 % |
| 31+ pcs | 178,00 € | −5 % |
Informácie o výrobku "ET-2254 Ethernet I/O Module, 16-ch Universal DIO with 2-port Switch"
The ET-2254 CR is an Ethernet I/O module offering 16 universal channels, each configurable as a digital input or a digital output. Its digital outputs are open-collector sink types rated at 100 mA per channel, with a load voltage of +5 ~ +30 VDC, while the digital inputs are source type. It suits engineers who need flexible I/O on an Ethernet network without a separate switch.
A built-in 2-port 10/100 Base-Tx switch with LAN bypass allows modules to be daisy-chained, which reduces cabling and network infrastructure. The module can also be configured through its web server, and access is protected by password and IP filter. Dual-watchdog functionality, along with programmable power-on and safe values for the digital outputs, helps keep the process in a defined state.
I/O Pair Connection lets local digital inputs be written to remote digital outputs in Push mode, or remote inputs be pulled to local outputs, over Ethernet using Modbus TCP. For higher-level systems, the module acts as an MQTT publisher and subscriber and supports SNMP V2c monitoring with optional Trap messages on I/O changes or restarts. Isolation is rated at 3000 VDC for I/O and 1500 VDC for Ethernet.
Applications
- Factory Automation
- Machine Automation
- Building Automation
- Remote Diagnosis & Maintenance
- Testing Equipment
| Product type: | Ethernet I/O Module |
|---|---|
| Interface: | Ethernet |
| Protocol: | Modbus TCP, Modbus UDP, MQTT, SNMP v2c |
| Digital inputs: | 16 |
| Digital outputs: | 16 |
| Ports: | 2 |
| Isolation: | 3000 VDC (I/O) |
| Power input: | +10 ~ +30 VDC |
| Operating temperature: | -25 ~ +75 °C |
| Mounting: | DIN-rail |
| Housing: | Plastic |
Specifications
| Software | |
|---|---|
| Built-in Web Server | Yes |
| CPU Module | |
| CPU | 32-bit ARM |
| Watchdog Timer | Module, Communication (Programmable) |
| Isolation | |
| 2-way Isolation | Ethernet: 1500 VDC I/O: 3000 VDC |
| EMS Protection | |
| EFT (IEC 61000-4-4) | ±4 kV for Power Line |
| ESD (IEC 61000-4-2) | ±8 kV Contact for Each Terminal ±16 kV Air for Random Point |
| Surge (IEC 61000-4-5) | ±3 kV for Power Line |
| LED Indicators | |
| Status | Run, Ethernet, I/O |
| Digital Input/Counter | |
| Type | Dry Contact |
| Sink/Source (NPN/PNP) | Source |
| ON Voltage Level | Close to GND |
| OFF Voltage Level | Open |
| Max. Counts | 4,294,967,295 (32-bit) |
| Frequency | 2.5 kHz |
| Input Impedance | 3 kΩ |
| Low Pass Filter | 1 ~ 6500 ms (0.08 Hz ~ 500 Hz) |
| Digital Output | |
| Type | Open-collector |
| Sink/Source (NPN/PNP) | Sink |
| Load Voltage | +5 ~ +30 VDC |
| Load Current | 100 mA/channel |
| Power on Value | Programmable |
| Safe Value | Programmable |
| Ethernet | |
| Ports | 2 x RJ-45, 10/100 Base-Tx, Switch Ports |
| LAN bypass | Yes |
| Access Control | Password and IP Filter |
| Protocol | Modbus TCP, Modbus UDP, MQTT, SNMP V2c |
| Power | |
| Reverse Polarity Protection | Yes |
| Consumption | 2.9 W (max.) |
| Powered from Terminal Block | +10 ~ +30 VDC |
| Mechanical | |
| Casing | Plastic |
| Dimensions (mm) | 33 x 126 x 108 (W x L x H) |
| Installation | DIN-Rail mounting |
| Environment | |
| Operating Temperature | -25 ~ +75 °C |
| Storage Temperature | -40 ~ +80 °C |
| Humidity | 10 ~ 90% RH, Non-condensing |
Specifications as published by the manufacturer. Subject to change.