PM-2133D-RCT4000P 3-Phase Power Meter, Modbus RTU, 4000 A Rogowski Coil
Modbus RTU three-phase power meter with 8-digit LED display and a 4000 A Rogowski coil CT set (185 mm inside diameter) for high-current energy monitoring.
- Current measurement up to 4000 A using three 185 mm inside diameter Rogowski coil CTs (5 A ~ 4000 A)
- True RMS voltage, current, power and energy readings with bi-directional energy measurement
- Energy analysis for 3P4W, 3P3W, 1P3W and 1P2W wiring configurations
- Voltage measurement up to 500 V, input range 10 ~ 500 V
- W accuracy better than 2% (PF=1) with input current above 200 A on the -4000P variant
- Total harmonic distortion (THD) measurement
1.500,00 EUR per piece
| 1–9 pcs | 1.500,00 EUR | |
|---|---|---|
| 10–30 pcs | 1.455,00 EUR | −3 % |
| 31+ pcs | 1.425,00 EUR | −5 % |
Informații despre produs "PM-2133D-RCT4000P 3-Phase Power Meter, Modbus RTU, 4000 A Rogowski Coil"
The PM-2133D-RCT4000P CR is a three-phase power meter with an 8-digit LED display, designed to show real-time electrical usage on low voltage primary and medium or high voltage secondary circuits. It records true RMS voltage, current and power values, together with active, apparent and reactive energy, and reports them over RS-485 using Modbus RTU.
This variant is supplied with three Rogowski coil CTs rated up to 4000 A, each with a 185 mm inside diameter and a 4 m wire lead. The flexible coil suits large conductors such as busway and installations where space is tight. The -4000P variant is rated for a W accuracy better than 2% (PF=1) at input currents above 200 A.
Energy analysis covers 3P4W, 3P3W, 1P3W and 1P2W wiring, with bi-directional energy measurement and total harmonic distortion (THD) reporting. The meter accepts a 10 ~ 500 V input range and has a 3000 VDC isolated RS-485 port.
Applications
- Generator monitoring
- Switchgear distribution systems
- Energy management
| Product type: | Power meter |
|---|---|
| Interface: | RS-485 |
| Protocol: | Modbus RTU |
| Ports: | 1 |
| Isolation: | 3000 VDC |
| Power input: | +85 ~ +264 VAC |
| Operating temperature: | -20 ~ +70 °C |
| Mounting: | Panel |
| Housing: | Plastic |
Specifications
| AC Power Measurement | |
|---|---|
| Wiring | 3P4W-3CT, 3P3W-2CT, 3P3W-3CT, 1P2W-1CT, 1P3W-2CT |
| Loops | 3-phase: 1; 1-phase: 3 @ 1P2W-1CT, 1 @ 1P3W-2CT |
| Input Voltage | 10 ~ 500 V |
| Input Current | PM-2133D-RCT500P: CTØ55 mm (5 A ~ 500 A) PM-2133D-RCT1000P: CTØ80 mm (5 A ~ 1000 A) PM-2133D-RCT2000P: CTØ105 mm (5 A ~ 2000 A) PM-2133D-RCT4000P: CTØ185 mm (5 A ~ 4000 A) |
| Input Frequency | 50 Hz (Range 45 ~ 55 Hz)/60 Hz (Range 55 ~ 65 Hz) |
| W Accuracy | Better than 2% (PF=1) Condition: Input current > 50A; (For -500P, -1000P) Input current > 200A; (For -2000P, -4000P) |
| Power Parameter Measurement | True RMS voltage (Vrms), True RMS current (Irms), Active Power (kW), Active Energy (kWh), Apparent Power (kVA), Apparent Energy (kVAh), Reactive Power (kVAR), Reactive Energy (kVARh), Power Factor (PF), Frequency (45 ~ 65 Hz) |
| Data Update Rate | 1 Second |
| LED Display | Yes, 8-digit |
| COM Ports | |
| Ports | 1 x RS-485 |
| Baud Rate | 9600, 19200 (default), 38400, 115200 |
| Data Format | N,8,1; N,8,2; E,8,1; E,8,2; O,8,1; O,8,2 |
| Protocol | Modbus RTU |
| Isolation | 3000 VDC |
| Power | |
| Input Range | +85 ~ +264 VAC (277 VAC available) |
| Consumption | 6 W |
| Mechanical | |
| Casing | Plastic |
| Dimensions (mm) | 110 x 115 x 50 (W x L x H) |
| Installation | Panel Mounting |
| Environment | |
| Operating Temperature | -20 ~ +70 °C |
| Storage Temperature | -25 ~ +80 °C |
| Humidity | 10 ~ 90% RH, Non-condensing |
Specifications as published by the manufacturer. Subject to change.