Sari la conținutul principal Sari la căutare Sari la navigarea principală

M-7017C-G 8-ch Current Input Module, DCON and Modbus RTU (Gray Cover)

Informații despre produs "M-7017C-G 8-ch Current Input Module, DCON and Modbus RTU (Gray Cover)"

M-7017C-G is an eight-channel RS-485 I/O module for engineers who only need to read current signals. Each differential input is measured directly, so there is no need to fit an external shunt resistor on the terminals, which keeps wiring and commissioning simple.

The module communicates over Modbus RTU or DCON, selectable through the configuration software. Inputs support ±20 mA, 0 ~ 20 mA and 4 ~ 20 mA ranges at 16-bit resolution with ±0.1% of FSR accuracy, and open wire detection is available for 4 ~ 20 mA loops. Hardware specifications match the I-7017C.

This gray-cover variant is the M-7017C-G ordering code offered here. It is intended for building, factory and machine automation, as well as remote maintenance, remote diagnosis and test equipment.

Applications

  • Building Automation
  • Factory Automation
  • Machine Automation
  • Remote Maintenance
  • Remote Diagnosis
  • Testing Equipment
Product type: Remote I/O module
Interface: RS-485
Protocol: DCON, Modbus RTU
Analog inputs: 8
Ports: 1
Isolation: 3000 VDC
Power input: +10 ~ +30 VDC
Operating temperature: -25 ~ +75 °C
Mounting: DIN-rail
Housing: Gray cover

Specifications

CPU Module
Watchdog TimerModule, Communication (Programmable)
Isolation
Intra-module Isolation3000 VDC
EMS Protection
EFT (IEC 61000-4-4)±4 kV for Power Line
ESD (IEC 61000-4-2)±4 kV Contact for Each Terminal
Surge (IEC 61000-4-5)±0.5 kV for Power Line
LED Indicators
Status1 x Power and Communication
Analog Input
Channels8 Differential
TypeCurrent
Range±20 mA, 0 ~ 20 mA, 4 ~ 20 mA
Resolution16-bit
Accuracy±0.1% of FSR
Sampling Rate10 Hz
Input ImpedanceCurrent: 125 Ω
Common Voltage Protection±15 VDC
Overcurrent Protection50 mA at 110 VDC
Open Wire DetectionFor 4 ~ 20 mA Only
COM Ports
Ports1 x RS-485
Baud Rate1200 ~ 115200 bps
Data Format(N, 8, 1), (N, 8, 2), (E, 8, 1), or (E, 8, 2)
ProtocolModbus RTU, DCON
Power
Reverse Polarity ProtectionYes
Input Range+10 ~ +30 VDC
Consumption1.3 W
Mechanical
Dimensions (mm)72 x 123 x 35 (W x L x H)
InstallationDIN-Rail Mounting
Environment
Operating Temperature-25 ~ +75 °C
Storage Temperature-40 ~ +85 °C
Humidity10 ~ 95% RH, Non-condensing

Specifications as published by the manufacturer. Subject to change.

0 din 0 recenzii

Evaluarea medie de 0 din 5 stele

Lasă o recenzie!