ET-7017-10 Ethernet I/O Module, 10/20-ch Analog Input
Ethernet I/O module with 10 differential or 20 single-ended analog inputs, software-selectable voltage and current ranges, and Modbus TCP/UDP communication over a single RJ-45 port.
- 10 differential or 20 single-ended analog input channels, software selectable
- Per-channel range selection from ±150 mV to ±20 mA, including 0 ~ 20 mA and 4 ~ 20 mA
- 16-bit resolution with normal mode (10 Hz total) and fast mode (50 Hz total) sampling
- Modbus TCP and Modbus UDP over a single 10/100 Base-TX RJ-45 port
- Built-in web server, web HMI and access control by ID, password and IP filter
- Dual watchdog with module and communication watchdog timers
266,00 € per piece
| 1–9 pcs | 266,00 € | |
|---|---|---|
| 10–30 pcs | 258,00 € | −3 % |
| 31+ pcs | 253,00 € | −5 % |
Produkta informācija "ET-7017-10 Ethernet I/O Module, 10/20-ch Analog Input"
The ET-7017-10 is an Ethernet-connected analog input module for engineers who need to bring a mix of voltage and current signals onto a network without a separate data acquisition unit. Each analog channel can be configured with its own input range, and the jumper settings determine whether a channel accepts voltage or current, so one module can serve several sensor types on the same panel.
Sampling can be run in normal mode at 10 Hz across all channels or in fast mode at 50 Hz across all channels, allowing the speed to be matched to the application. The module provides a 16-bit resolution, with an accuracy of ±0.1% in normal mode and ±0.5% or better in fast mode. Overvoltage protection is rated at 240 Vrms for differential inputs and 150 Vrms for single-ended inputs.
Communication is handled through one 10/100 Base-TX RJ-45 port supporting Modbus TCP and Modbus UDP, with ID, password and IP filter access control. A built-in web server and web HMI, along with dual watchdogs, support commissioning and supervision. The module is powered from a +10 ~ +30 VDC terminal block and mounts on a DIN-rail.
Applications
- Building Automation
- Factory Automation
- Machine Automation
- Remote Maintenance
- Remote Diagnosis
- Testing Equipment
| Product type: | Ethernet I/O Module |
|---|---|
| Interface: | Ethernet |
| Protocol: | Modbus TCP, Modbus UDP |
| Analog inputs: | 10/20 |
| Ports: | 1 |
| Isolation: | Ethernet 1500 VDC, I/O 2500 VDC |
| Power input: | +10 ~ +30 VDC |
| Operating temperature: | -25 ~ +75 °C |
| Mounting: | DIN-rail |
Specifications
| Software | |
|---|---|
| Built-in Web Server | Yes |
| CPU Module | |
| Watchdog Timer | Module, Communication (Programmable) |
| Isolation | |
| 2-way Isolation | Ethernet: 1500 VDC I/O: 2500 VDC |
| EMS Protection | |
| EFT (IEC 61000-4-4) | ±4 kV for Power Line |
| ESD (IEC 61000-4-2) | ±4 kV Contact for Each Terminal ±8 kV Air for Random Point |
| Surge (IEC 61000-4-5) | ±0.5 kV for Power Line |
| LED Indicators | |
| Status | Run, Ethernet |
| Analog Input | |
| Channels | 10 differential or 20 single-ended (Note1), software selectable |
| Type | Voltage Current |
| Range | ±150 mV, ±500 mV, ±1 V, ±5 V, ±10 V ±20 mA, 0 ~ 20 mA, 4 ~ 20 mA (Jumper Selectable) |
| Resolution | 16-bit |
| Accuracy | Normal Mode: ±0.1% Fast Mode: ±0.5% or better |
| Sampling Rate | Normal Mode: 10 Hz (total channels) Fast Mode: 50 Hz (total channels) |
| Input Impedance | Voltage: 2 MΩ (Differential), 1 MΩ (Single-ended) Current: 125 Ω |
| Common Voltage Protection | ±200 VDC |
| Overvoltage Protection | Differential: 240 Vrms Single-ended: 150 Vrms |
| Overcurrent Protection | 50 mA at 110 VDC (max.) |
| Individual Channel Configuration | Yes |
| Open Wire Detection | For 4 ~ 20 mA only |
| Isolation | ±400 VDC, Virtual Channel to Channel Isolation |
| Ethernet | |
| Ports | 1 x RJ-45, 10/100 Base-TX |
| Access Control | ID, Password and IP Filter |
| Protocol | Modbus TCP, Modbus UDP |
| Power | |
| Reverse Polarity Protection | Yes |
| Consumption | 2.8 W (max.) |
| Powered from Terminal Block | +10 ~ +30 VDC |
| Mechanical | |
| Dimensions (mm) | 72 x 123 x 35 (W x L x H) |
| Installation | DIN-Rail mounting |
| Environment | |
| Operating Temperature | -25 ~ +75 °C |
| Storage Temperature | -30 ~ +80 °C |
| Humidity | 10 ~ 90% RH, Non-condensing |
Specifications as published by the manufacturer. Subject to change.