tM-AD8 8-Channel Isolated Analog Input Module, Voltage, RS-485
Eight single-ended voltage inputs with programmable ranges up to 0 ~ 10 V, 120 VDC overvoltage protection and RS-485 with DCON or Modbus RTU/ASCII for distributed I/O.
- Eight single-ended voltage inputs with programmable ranges from 0 ~ 500 mV to 0 ~ 10 V
- Selectable normal (10 Hz, 14-bit, ±0.1%) or fast (200 Hz, 12-bit, ±0.5%) sampling
- 120 VDC overvoltage protection and 10 MΩ input impedance
- 2500 VDC intra-module isolation and ±4 kV contact ESD protection per terminal
- Programmable dual watchdog for module and communication
- RS-485 port with DCON, Modbus RTU and Modbus ASCII at 1200 ~ 115200 bps
138,00 € per piece
| 1–9 pcs | 138,00 € | |
|---|---|---|
| 10–30 pcs | 134,00 € | −3 % |
| 31+ pcs | 131,00 € | −5 % |
Info sui prodotti "tM-AD8 8-Channel Isolated Analog Input Module, Voltage, RS-485"
The tM-AD8 CR brings eight single-ended voltage inputs onto an RS-485 network, making it a practical choice for collecting analogue signals in distributed automation cabinets. Each input can be set to one of five ranges, from 0 ~ 500 mV up to 0 ~ 10 V, so one module can accept a range of voltage-output sensors and transmitters.
Sampling can be chosen between a normal mode at 10 Hz with 14-bit resolution and ±0.1% accuracy, and a fast mode at 200 Hz with 12-bit resolution and ±0.5% accuracy. The input impedance is 10 MΩ, and the inputs tolerate overvoltage up to 120 VDC.
For harsher installations, the module provides 2500 VDC intra-module isolation and ±4 kV contact ESD protection on each terminal. A programmable dual watchdog covers both the module and communication, and reverse polarity protection is fitted on the 10 ~ 30 VDC supply. It mounts on DIN rail and operates from -25 ~ +75 °C.
Applications
- Industrial automation
- Industrial machinery
- Building automation
- Food and beverage systems
- Semiconductor fabrication
- Control systems
| Product type: | Analog Input Module |
|---|---|
| Interface: | RS-485 |
| Protocol: | DCON, Modbus ASCII, Modbus RTU |
| Analog inputs: | 8 |
| Ports: | 1 |
| Isolation: | 2500 VDC |
| Power input: | 10 ~ 30 VDC |
| Operating temperature: | -25 ~ +75 °C |
| Mounting: | DIN-rail |
Specifications
| CPU Module | |
|---|---|
| Watchdog Timer | Module, Communication (Programmable) |
| Isolation | |
| Intra-module Isolation | 2500 VDC |
| EMS Protection | |
| EFT (IEC 61000-4-4) | ±4 kV for Power |
| ESD (IEC 61000-4-2) | ±4 kV Contact for Each Terminal ±8 kV Air for Random Point |
| LED Indicators | |
| Status | 1 x Power and Communication |
| Analog Input | |
| Channels | 8 Single-ended |
| Type | Voltage |
| Range | 0 ~ 500 mV, 0 ~ 1 V, 0 ~ 2.5 V, 0 ~ 5 V, 0 ~ 10 V |
| Resolution | Normal Mode: 14-bit Fast Mode: 12-bit |
| Accuracy | Normal Mode: ±0.1% Fast Mode: ±0.5% |
| Sampling Rate | Normal Mode: 10 Hz Fast Mode: 200 Hz |
| Input Impedance | 10 MΩ |
| Overvoltage Protection | 120 VDC |
| COM Ports | |
| Ports | 1 x RS-485 |
| Baud Rate | 1200 ~ 115200 bps |
| Data Format | (N, 8, 1), (N, 8, 2), (O, 8, 1), (E, 8, 1) |
| Protocol | DCON, Modbus RTU, Modbus ASCII |
| Power | |
| Reverse Polarity Protection | Yes |
| Consumption | 0.7 W max. |
| Powered from Terminal Block | 10 ~ 30 VDC |
| Mechanical | |
| Dimensions (mm) | 52 x 98 x 27 (W x L x H) |
| Installation | DIN-Rail Mounting |
| Environment | |
| Operating Temperature | -25 ~ +75 °C |
| Storage Temperature | -30 ~ +75 °C |
| Humidity | 10 ~ 95% RH, Non-condensing |
Specifications as published by the manufacturer. Subject to change.