DNM-831I-100V-50A Voltage Attenuator and Current Transformer, ±100 V / ±50 A
Signal conditioner that scales a ±100 V input to ±10 V and a ±50 A current to ±10 V for measurement by standard analog input modules, with 3000 VDC isolation.
- Scales ±100 VDC to ±10 V on the voltage channel and ±50 A to ±10 V on the current channel
- 3000 VDC intra-module and channel-to-channel isolation
- Linear attenuation ratio with high input impedance
- Clip-type current transformer, Φ21 mm inside diameter, 1.5 m leading cable
- Voltage channel bandwidth 20 Hz ~ 20 kHz; current channel bandwidth 0 ~ 50 KHz
- Metal casing, DIN-rail mounting, 103 x 93 x 29 mm
208,00 € per piece
| 1–9 pcs | 208,00 € | |
|---|---|---|
| 10–30 pcs | 202,00 € | −3 % |
| 31+ pcs | 197,00 € | −5 % |
Info sui prodotti "DNM-831I-100V-50A Voltage Attenuator and Current Transformer, ±100 V / ±50 A"
The DNM-831I-100V-50A CR combines one high-voltage channel and one high-current channel in a single DIN-rail module. Inputs of up to ±100 VDC and ±50 A are attenuated to a ±10 V output, so they can be read by analog input modules that expect a standard voltage signal.
Each input is isolated from its output and from the other channel, with 3000 VDC isolation between modules and between channels. This helps keep noise from the high-voltage and high-current circuits out of the measurement path. The current input uses the supplied clip-type current transformer with a 21 mm aperture and a 1.5 m lead.
The order includes the CA-040415 cable and the ASO-0002 current transformer. The module is housed in metal, operates from +10 VDC to +30 VDC and is rated for -25 ~ +75 °C. It carries CE, UKCA, FCC, RoHS and WEEE marks.
Applications
- High-voltage measurement with analog input modules
- High-current measurement with analog input modules
- Monitoring of AC and DC voltage and current signals in industrial control panels
| Product type: | Voltage attenuator and current transformer |
|---|---|
| Analog inputs: | 2 |
| Analog outputs: | 2 |
| Isolation: | 3000 VDC |
| Power input: | +10 VDC ~ +30 VDC |
| Operating temperature: | -25 ~ +75 °C |
| Mounting: | DIN-rail |
| Housing: | Metal |
Specifications
| EMS Protection | |
|---|---|
| ESD (IEC 61000-4-2) | ±4 kV contact for power line, input and output channels, ±8 kV air for random point |
| Surge (IEC 61000-4-5) | ±3 kV for power liner |
| CT | |
| Type | Clip |
| Inside Diameter | Φ21 mm |
| Leading Cable | 1.5 m |
| Analog Input | |
| Channels | High Current: 1 High Voltage: 1 |
| Type | AC/DC Current AC/DC Voltage |
| Range | High Current: ±50 A High Voltage: ±100 VDC |
| Accuracy | High Current: 1% of FSR High Voltage: 1% of FSR |
| Bandwidth | High Current: 0 ~ 50 KHz High Voltage: 20 Hz ~ 20 kHz |
| Isolation | High Current: 2.5 KV @ 50 (60) HZ/1 min |
| Analog Output | |
| Channels | High Current: 1 High Voltage: 1 |
| Type | AC/DC Current AC/DC Voltage |
| Range | • High Current: ±10 VDC or 10 VAC • High Voltage: ±10 VDC or 10 VAC |
| Power | |
| Input Range | +10 VDC ~ +30 VDC |
| Consumption | 1.8 W |
| Mechanical | |
| Casing | Metal |
| Dimensions (mm) | 103 x 93 x 29 (W x L x D) |
| Installation | DIN-Rail Mounting |
| Environment | |
| Operating Temperature | -25 ~ +75 °C |
| Storage Temperature | -30 ~ +75 °C |
| Humidity | 10 ~ 90% RH, Non-condensing |
Specifications as published by the manufacturer. Subject to change.