The I-7590 bridges a serial host to M-Bus (Meter-Bus) slave devices. It accepts RS-232, RS-422 or RS-485 on the serial side and passes data through to the M-Bus network, so a standard serial master can poll energy counters, water and gas meters, and other M-Bus instruments without a custom protocol stack.

Serial and M-Bus baud rates can be configured separately. Ten default baud rates and six user-defined rates are available, allowing the converter to match a wide range of meter configurations. Transparent communication means the converter does not alter the data stream, and it supports up to 100 M-Bus slaves.

For reliability in the field, the M-Bus port has 3750 Vrms photocoupler isolation along with overcurrent and short-circuit protection. The unit also includes a watchdog, reverse polarity protection on the power input, and firmware can be updated through the RS-232 port. It mounts on DIN-rail and is rated for -25 ~ +75 ℃ operation.

Applications

  • Remote reading of energy counters
  • Hot and cold water meter reading
  • Gas meter and gas counter reading
  • Pressure sensors and actuators on M-Bus networks
Product type: Converter
Interface: RS-232/422/485
Protocol: M-Bus
Ports: 1
Isolation: 3750 Vrms
Operating temperature: -25 ~ +75 °C
Mounting: DIN-rail

Specifications

COM Ports
Ports1 x RS-232/485/422, Non-isolated
Baud Rate300 ~ 115200 bps
ParityNone, Even, Odd, Mark, Space
Data Bit5, 6, 7, 8
Stop Bit1, 2
M-Bus
Ports1
Baud Rate300 ~ 2400 bps and user-defined baud rate
Data Bit5, 6, 7, 8
Stop Bit1, 2
ParityNone, Even, Odd, Space, Mark
Isolation3750 Vrms for photo-couple
Current Protectionshort-circuit protection
Power
Consumption1.8 W @ 24 VDC (with 1 slave device), 11.8 W @ 24 VDC (with 100 slave devices)
Mechanical
Dimensions (mm)72 x 120 x 36 (W x H x D)
InstallationDIN-Rail
Environment
Operating Temperature-25 ~ +75 ℃
Storage Temperature-30 ~ +80 ℃
Humidity10 ~ 90% RH, Non-condensing

Specifications as published by the manufacturer. Subject to change.