Ugrás a fő tartalomra Ugrás a kereséshez Ugrás a fő navigációhoz

LC-101H Lighting Control Module, 1-CH, 0-5 A AC Load Current Measurement

Termékinformációk "LC-101H Lighting Control Module, 1-CH, 0-5 A AC Load Current Measurement"

The LC-101H CR is a single-loop lighting control module for smart home and building lighting circuits. Each circuit can be switched on or off remotely over RS-485, locally through a physical switch, or with both methods used separately or combined.

The module measures the AC load current on the lighting circuit in the 0 to 5 A range, so the controller can read back the current value over RS-485. This helps identify faulty lights and shows whether the circuit is on or off. The high-power relay is designed to withstand the inrush currents that inductive lighting loads produce when switched, which helps protect the relay and reduce maintenance.

No software is needed for basic channel control. When software control is required, the module communicates using Modbus RTU, with the RS-485 address set by hardware.

Applications

  • Smart home lighting control
  • Building automation lighting circuits
  • Remote switching and status monitoring of lighting loads
Product type: Lighting control module
Interface: RS-485
Protocol: Modbus RTU/DCON
Digital inputs: 1
Relay outputs: 1
Analog inputs: 1 (AC current)
Ports: 1
Isolation: 3000 VDC
Power input: 10 ~ 30 VDC
Operating temperature: -25 ~ +75 °C
Mounting: DIN-rail

Specifications

Software
FunctionLocal and Remote Direct Control Relay ON/OFF and Remote Status Monitoring
EMS Protection
EFT (IEC 61000-4-4)±4 kV for Power
ESD (IEC 61000-4-2)±4 kV Contact for each Terminal
Surge (IEC 61000-4-5)±2 kV for Power
LED Indicators
Status1 LED as Power Indicator
Digital Input
Channels1
TypeWet Contact, 90 ~ 240 VAC
ON Voltage Level65 VAC
OFF Voltage Level56 VAC
Isolation3000 VDC
Input Impedance68 KΩ, 2W
Relay Output
Channels1
TypePower Relay, Form C (SPDT N.O+N.C..)
Contact Rating30 A @ 250 VAC
AC Load Current MeasurementYes, 0 ~ 5 A range with 3% of FSR Accuracy.
Operate Time15 ms Max
Release Time22 ms Max.
Electrical Endurance100,000 ops.
Mechanical Endurance10,000,000 ops
Power on ValueYes
Safe ValueYes
Application Specification(1).Incandescent Lamp: 40W/ 220VAC * 5 Sets
(2).LED(Electronic ballast): 40W/ 220VAC *8 Sets
Ethernet
Node Address32 to 63 for hardware configuration
COM Ports
Ports1 x RS-485
Baud RateHardware Configuration: Fixed 9600 bps
Software Configuration: 1200 to 115200 bps
Data FormatN,8,1/O,8,1/E,8,1/N,8,2
ProtocolModbus RTU/DCON
Power
Reverse Polarity ProtectionYes
Input Range10 ~ 30 VDC
Consumption1.9 W Max.
Mechanical
Dimensions (mm)72 mm x 95 mm x 57 mm
InstallationDIN-Rail
Environment
Operating Temperature-25 ~ +75°C
Storage Temperature-30 ~ +75°C
Humidity10 ~ 95% RH, Non-condensing

Specifications as published by the manufacturer. Subject to change.

0 az 0 értékelésből

Átlagos értékelés 0 a 5 csillagból

Hagyj egy kritikát!

Ossza meg tapasztalatait más ügyfelekkel.