R-9015 12-ch RTD Input Module, RIO-98x0 Redundant I/O
12-channel, 16-bit RTD input module for Pt100, JPt100 and Pt1000 sensors, with channel and terminal board disconnection detection and redundancy support in RIO-98x0 systems.
- 12 RTD input channels for Pt100, JPt100 and Pt1000 sensors
- 16-bit A/D converter with ±0.05% FSR accuracy
- User-defined measurement range scaling and temperature offset
- High and low alarm for abnormal channel temperatures
- Channel disconnection and termination board disconnection detection
- Redundant switching time below 1 ms in RIO-98x0 systems
1 363,00 € per piece
| 1–9 pcs | 1 363,00 € | |
|---|---|---|
| 10–30 pcs | 1 322,00 € | −3 % |
| 31+ pcs | 1 295,00 € | −5 % |
Informations sur le produit "R-9015 12-ch RTD Input Module, RIO-98x0 Redundant I/O"
The R-9015 CR is a 12-channel RTD temperature input module for the RIO-98x0 redundant I/O system. It accepts Pt100, JPt100 and Pt1000 sensors, with a measurement accuracy of ±0.05% FSR and a 16-bit A/D converter. Measurement ranges and temperature offsets can be set to suit each application, and high and low alarms flag abnormal channel temperatures immediately.
Wiring integrity is monitored at two levels. The module detects channel disconnections and also detects when the termination board is disconnected. The R-9015 CR must be used with an RDB-S03 or RDB-D03 terminal board to connect field signals. Power supply and backplane bus are isolated at 3000 VDC, which helps reduce noise interference in industrial environments.
Redundancy is supported, so the system can continue to operate if a single I/O module fails, with a redundant switching time of less than 1 ms. This version is the RoHS-compliant variant of the 12-ch RTD Input Module.
Applications
- Building automation
- Factory automation
- Machine automation
- Remote maintenance
- Remote diagnosis
- Testing equipment
| Product type: | RTD Input Module |
|---|---|
| Analog inputs: | 12 |
| Isolation: | 3000 VDC |
| Operating temperature: | -25 ~ +70 °C |
Specifications
| EMS Protection | |
|---|---|
| EFT (IEC 61000-4-4) | Yes |
| ESD (IEC 61000-4-2) | Yes |
| LED Indicators | |
| Status | 1 PWR, 1 MOD, 1 ACT, 1 DX, 1 ERR LED 0~11 for CH High/Low Alarm LED 16~27 for CH Break Line |
| Analog Input | |
| Channels | 12 |
| Type | RTD |
| Sensor Type | Pt100, JPt100, Pt1000 |
| Range | Pt100: -200 ~ +850 ℃ JPt100, Pt1000: -200 ~ +630 ℃ |
| Resolution | 16 bit |
| Accuracy | ±0.05% FSR (±250 mΩ) |
| Sampling Rate | 1 Samples/sec (Total) |
| Input Impedance | 20 MΩ |
| Common Mode Rejection | 106 dB |
| Normal Mode Rejection | 100 dB |
| Open Wire Detection | Yes |
| Zero Drift | ±0.5 μV/°C |
| Span Drift | ±20 ppm/°C |
| Isolation | 3000 VDC |
| I/O Expansion | |
| I/O Type | RDB-S03 / RDB-D03 |
| Power | |
| Consumption | 2 W |
| Mechanical | |
| Dimensions (mm) | 33 x 129 x 130 |
| Environment | |
| Operating Temperature | -25 °C ~ +70 °C |
| Humidity | 5 ~ 95% RH, Non-condensing |
Specifications as published by the manufacturer. Subject to change.