I-7015P-G 6-ch RTD Input Module, 3-wire Lead Resistance Elimination, DCON
6-channel RTD input module with automatic 3-wire lead resistance elimination, aimed at long-distance temperature measurement over RS-485 with the DCON protocol.
- 6 RTD inputs, with individual channel configuration for mixed sensor types
- Automatic lead resistance elimination for 3-wire RTD connections
- 16-bit resolution with ±0.05% of FSR accuracy
- Open wire detection on each channel
- 1 x RS-485 port with DCON protocol, 1200 ~ 115200 bps
- 3000 VDC intra-module isolation and ±4 kV ESD protection
315,00 € per piece
| 1–9 pcs | 315,00 € | |
|---|---|---|
| 10–30 pcs | 306,00 € | −3 % |
| 31+ pcs | 299,00 € | −5 % |
Informations sur le produit "I-7015P-G 6-ch RTD Input Module, 3-wire Lead Resistance Elimination, DCON"
The I-7015P-G CR is a 6-channel RTD input module for temperature measurement with Pt100, Pt1000, Ni120, Cu50, Cu100 and Cu1000 sensors. Each channel can be configured individually, so different sensor types can be connected to the same module. Automatic compensation for 3-wire RTD connections keeps readings accurate regardless of cable length, which makes this variant suited to long sensor runs.
Engineers will value the 16-bit resolution, open wire detection and dual watchdog, which together help keep measurements reliable and fault conditions visible. The module offers 3000 VDC intra-module isolation and ±4 kV ESD protection on each terminal, and it is controlled via a single RS-485 port using DCON. The gray cover distinguishes this ordering code within the I-7015 series.
Key electrical and mechanical details include a +10 ~ +30 VDC power input with reverse polarity protection, a 1.2 W power consumption, DIN-rail mounting and an operating range of -25 ~ +75 °C.
Applications
- Building Automation
- Factory Automation
- Machine Automation
- Remote Maintenance
- Remote Diagnosis
- Testing Equipment
| Product type: | RTD Input Module |
|---|---|
| Interface: | RS-485 |
| Protocol: | DCON |
| Analog inputs: | 6 |
| Ports: | 1 |
| Isolation: | 3000 VDC |
| Power input: | +10 ~ +30 VDC |
| Operating temperature: | -25 ~ +75 °C |
| Mounting: | DIN-rail |
| Housing: | Gray |
Specifications
| CPU Module | |
|---|---|
| Watchdog Timer | Module, Communication (Programmable) |
| Isolation | |
| Intra-module Isolation | 3000 VDC |
| EMS Protection | |
| EFT (IEC 61000-4-4) | ±4 kV for Power Line |
| ESD (IEC 61000-4-2) | ±4 kV Contact for Each Terminal |
| LED Indicators | |
| Status | 1 x Power and Communication |
| Analog Input | |
| Channels | 6 |
| Type | RTD |
| Sensor Type | Pt100, Pt1000, Ni120, Cu50, Cu100, Cu1000 |
| Resistance Measurement | 3.2 kΩ max. |
| Resolution | 16-bit |
| Accuracy | ±0.05% of FSR |
| Sampling Rate | 12 Hz (Total) |
| Overvoltage Protection | 120 VDC |
| Individual Channel Configuration | Yes |
| Open Wire Detection | Yes |
| 3-wire RTD Lead Resistance Elimination | Yes |
| COM Ports | |
| Ports | 1 x RS-485 |
| Baud Rate | 1200 ~ 115200 bps |
| Data Format | (N, 8, 1), (N, 8, 2), (E, 8, 1), or (O, 8, 1) |
| Protocol | DCON |
| Power | |
| Reverse Polarity Protection | Yes |
| Input Range | +10 ~ +30 VDC |
| Consumption | 1.2 W |
| Mechanical | |
| Dimensions (mm) | 72 x 123 x 35 (W x L x H) |
| Installation | DIN-Rail Mounting |
| Environment | |
| Operating Temperature | -25 ~ +75 °C |
| Storage Temperature | -40 ~ +85 °C |
| Humidity | 10 ~ 95% RH, Non-condensing |
Specifications as published by the manufacturer. Subject to change.
Downloads