M-7018-G 8-ch Thermocouple Input Module, Modbus RTU/DCON
8-channel differential analog input module for voltage, current and thermocouple signals, with RS-485 communication over Modbus RTU or DCON. Gray cover.
- Eight differential analog inputs for voltage, current and thermocouple signals
- Thermocouple support for types J, K, T, E, R, S, B, N and C
- 16-bit resolution with ±0.1% of FSR accuracy
- 3000 VDC intra-module isolation and ±4 kV ESD protection on each terminal
- One RS-485 port with Modbus RTU and DCON protocols, configured via software
- Programmable module and communication watchdog
230,00 € per piece
| 1–9 pcs | 230,00 € | |
|---|---|---|
| 10–30 pcs | 223,00 € | −3 % |
| 31+ pcs | 219,00 € | −5 % |
Toote teave "M-7018-G 8-ch Thermocouple Input Module, Modbus RTU/DCON"
The M-7018-G CR is a DIN-rail remote I/O module that takes in eight differential analog channels and accepts voltage, current or thermocouple signals on the same hardware. Readings are sent over a single RS-485 port, so it suits distributed measurement in cabinets and across machines where a serial network is already in place.
Each channel supports a wide selection of thermocouple types (J, K, T, E, R, S, B, N and C) as well as a range of voltage and current spans, with 16-bit resolution. Channel-to-channel and module-to-bus isolation of 3000 VDC, together with 4 kV ESD protection on each terminal, help the unit tolerate electrically noisy industrial environments.
Modbus RTU and DCON are selectable through software, and the module includes a programmable watchdog for module and communication monitoring. Typical deployments include:
- Building automation
- Factory and machine automation
- Remote maintenance and diagnosis
- Test equipment
Applications
- Building automation
- Factory automation
- Machine automation
- Remote maintenance
- Remote diagnosis
- Testing equipment
| Product type: | Analog Input Module |
|---|---|
| Interface: | RS-485 |
| Protocol: | DCON, Modbus RTU |
| Analog inputs: | 8 |
| Ports: | 1 |
| Isolation: | 3000 VDC |
| Power input: | +10 ~ +30 VDC |
| Operating temperature: | -25 ~ +75 °C |
| Mounting: | DIN-rail |
| Housing: | Gray |
Specifications
| CPU Module | |
|---|---|
| Watchdog Timer | Module, Communication (Programmable) |
| Isolation | |
| Intra-module Isolation | 3000 VDC |
| EMS Protection | |
| EFT (IEC 61000-4-4) | ±4 kV for Power Line |
| ESD (IEC 61000-4-2) | ±4 kV Contact for Each Terminal |
| Surge (IEC 61000-4-5) | ±0.5 kV for Power Line |
| LED Indicators | |
| Status | 1 x Power and Communication |
| Analog Input | |
| Channels | 8 Differential |
| Type | Voltage Current Thermocouple |
| Sensor Type | Thermocouple: J, K, T, E, R, S, B, N, C |
| Range | Voltage: ±15 mV, ±50 mV, ±100 mV, ±500 mV, ±1 V, ±2.5 V Current: ±20 mA, 0 ~ +20 mA, +4 ~ +20 mA (requires an optional external 125 Ω resistor) |
| Resolution | 16-bit |
| Accuracy | ±0.1% of FSR |
| Sampling Rate | 10 Hz (Total) |
| Input Impedance | > 400 kΩ |
| Common Voltage Protection | 25 VDC |
| Overvoltage Protection | ±120 VDC |
| COM Ports | |
| Ports | 1 x RS-485 |
| Baud Rate | 1200 ~ 115200 bps |
| Data Format | (N, 8, 1), (N, 8, 2), (E, 8, 1), or (O, 8, 1) |
| Protocol | Modbus RTU, DCON |
| Power | |
| Reverse Polarity Protection | Yes |
| Input Range | +10 ~ +30 VDC |
| Consumption | 1.0 W |
| Mechanical | |
| Dimensions (mm) | 72 x 123 x 35 (W x L x H) |
| Installation | DIN-Rail Mounting |
| Environment | |
| Operating Temperature | -25 ~ +75 °C |
| Storage Temperature | -40 ~ +85 °C |
| Humidity | 10 ~ 95% RH, Non-condensing |
Specifications as published by the manufacturer. Subject to change.