Preskoči na glavno vsebino Preskoči na iskanje Preskoči na glavno navigacijo

PM-3112-160P-CPS CANopen 2-Loop Single-Phase Power Meter, 100 A CT

Informacije o izdelku "PM-3112-160P-CPS CANopen 2-Loop Single-Phase Power Meter, 100 A CT"

PM-3112-160P-CPS CR is a DIN-rail power meter that reports real-time electrical usage for two independent single-phase loops over CANopen. Each loop has its own reference voltage, so one unit can cover two feeds in a compact enclosure.

This variant is fitted with two 100 A clip-on current transformers with a 16 mm inside diameter and 4 m wire leads, which makes installation on existing conductors straightforward. The voltage input accepts 10 ~ 300 VAC, and two Form A power relay outputs rated 5 A @ 250 VAC or 30 VDC can drive sirens or lights for alarm signalling.

  • Measures Vrms, Irms, kW, kWh, kVA, kVAh, kVAR, kVARh, power factor and frequency
  • Updates data every second
  • Designed for use on generator, switchgear and distribution circuits

Applications

  • Generator monitoring
  • Switchgear distribution systems
  • Energy management
Product type: Power meter
Interface: CANopen
Protocol: CANopen
Relay outputs: 2
Power input: +12 ~ 48 VDC
Operating temperature: -20 ~ +70 °C
Mounting: DIN-rail
Housing: Plastic

Specifications

AC Power Measurement
Wiring1P2W-1CT
Loops1-phase: 2
Input Voltage10 ~ 300 V
Input CurrentPM-3112-100-CPS: CTØ10 mm (0.05 A ~ 60 A)
PM-3112-100P-CPS: CTØ10 mm (0.05 A ~ 60 A)
PM-3112-160-CPS: CTØ16 mm (0.1 A ~ 100 A)
PM-3112-160P-CPS: CTØ16 mm (0.1 A ~ 100 A)
PM-3112-240-CPS: CTØ24 mm (0.15 A ~ 200 A)
PM-3112-240P-CPS: CTØ24 mm (0.15 A ~ 200 A)
Input Frequency50/60 Hz
W AccuracyBetter than 0.5% (PF=1)
Power Parameter MeasurementTrue RMS voltage (Vrms), True RMS current (Irms), Active Power (kW), Active Energy (kWh), Apparent Power (kVA), Apparent Energy (kVAh), Reactive Power (kVAR), Reactive Energy (kVARh), Power Factor (PF), Frequency
Data Update Rate1 Second
Relay Output
Channels2
TypePower Relay
Contact RatingForm A:
5 A @ 250 VAC
5 A @ 30 VDC
CANopen
Baud Rate125 k (default), 250 k, 500 k, 1 M; DIP Switch Selectable
ProtocolCANopen
Power
Input Range+12 ~ 48 VDC
Consumption2W
Mechanical
CasingPlastic
Dimensions (mm)33 x 127 x 100 (W x L x H)
InstallationDIN-Rail Mounting
Environment
Operating Temperature-20 ~ +70 °C
Storage Temperature-25 ~ +80 °C
Humidity10 ~ 90% RH, Non-condensing

Specifications as published by the manufacturer. Subject to change.

0 od 0 ocen

Povprečna ocena 0 od 5 zvezdic

Pustite pregled!