tM-AD4P2C2 RS-485 Multifunction I/O Module, 4-ch AI, 2-ch DI, 2-ch DO
Isolated tM series RS-485 module combining 4 analog inputs, 2 wet-contact digital inputs and 2 sink-type digital outputs. Supports DCON, Modbus RTU and Modbus ASCII.
- Two voltage inputs (±1 V, ±2.5 V, ±5 V, ±10 V) and two current inputs (±20 mA, 0 ~ 20 mA, 4 ~ 20 mA), individually configurable
- Selectable analog sampling: normal mode 10 Hz at 14-bit, fast mode 200 Hz at 12-bit
- Two digital inputs usable as 16-bit counters (maximum 65535 counts, 50 Hz frequency)
- Two isolated sink-type digital outputs with short-circuit protection, 700 mA per channel, usable as voltage input limit alarms
- Programmable power-on and safe values for digital outputs
- 2500 VDC intra-module isolation and ±4 kV ESD contact protection for each terminal
133,00 € per piece
| 1–9 pcs | 133,00 € | |
|---|---|---|
| 10–30 pcs | 129,00 € | −3 % |
| 31+ pcs | 126,00 € | −5 % |
Informações de produto "tM-AD4P2C2 RS-485 Multifunction I/O Module, 4-ch AI, 2-ch DI, 2-ch DO"
The tM-AD4P2C2 is a compact DIN-rail I/O module that brings analog measurement, digital sensing and switched output into one unit on an RS-485 bus. Its two voltage and two current input channels cover a choice of standard signal ranges, so one module can handle mixed sensor types without extra signal conditioning.
Each analog channel can be configured individually, with a selectable sampling mode: a normal mode at 10 Hz with 14-bit resolution, or a fast mode at 200 Hz with 12-bit resolution. The two digital inputs can also be used as 16-bit counters, and the two sink-type outputs can act as voltage input limit alarms, which helps when you need local alarm behaviour alongside data acquisition.
Power-on and safe values for the digital outputs are programmable, and the module offers dual watchdog protection covering both the module and communication. The 2500 VDC intra-module isolation and the listed ESD and EFT immunity ratings make it suitable for electrically demanding cabinets. Communication uses DCON, Modbus RTU or Modbus ASCII, selected through software.
Applications
- Industrial Automation
- Industrial Machinery
- Building Automation
- Control Systems
- Food and Beverage Systems
- Semiconductor Fabrication
| Product type: | Remote I/O module |
|---|---|
| Interface: | RS-485 |
| Protocol: | DCON, Modbus ASCII, Modbus RTU |
| Digital inputs: | 2 |
| Digital outputs: | 2 |
| Analog inputs: | 4 |
| Ports: | 1 |
| Isolation: | 2500 VDC |
| Power input: | 10 ~ 30 VDC |
| Operating temperature: | -25 ~ +75 °C |
| Mounting: | DIN-rail |
Specifications
| CPU Module | |
|---|---|
| Watchdog Timer | Module, Communication (Programmable) |
| Isolation | |
| Intra-module Isolation | 2500 VDC |
| EMS Protection | |
| EFT (IEC 61000-4-4) | ±4 kV for Power |
| ESD (IEC 61000-4-2) | ±4 kV Contact for Each Terminal ±8 kV Air for Random Point |
| LED Indicators | |
| Status | 1 x Power and Communication |
| Analog Input | |
| Channels | Voltage: 2 Single-ended Current: 2 Single-ended |
| Range | Voltage: ±1 V, ±2.5 V, ±5 V, ±10 V Current: ±20 mA, 0 ~ 20 mA, 4 ~ 20 mA |
| Resolution | Normal Mode: 14-bit Fast Mode: 12-bit |
| Accuracy | Normal Mode: ±0.1% Fast Mode: ±0.5% |
| Sampling Rate | Normal Mode: 10 Hz Fast Mode: 200 Hz |
| Input Impedance | Voltage: 10 MΩ Current: 136 Ω |
| Overvoltage Protection | 120 VDC |
| Overcurrent Protection | 50 mA at 110 VDC |
| Individual Channel Configuration | Yes |
| Digital Input/Counter | |
| Channels | 2 |
| Type | Wet Contact |
| Sink/Source (NPN/PNP) | Source |
| ON Voltage Level | +3.5 ~ +50 VDC |
| OFF Voltage Level | +1 VDC max. |
| Max. Counts | 65535 (16-bit) |
| Frequency | 50 Hz |
| Min. Pulse Width | 10 ms |
| Input Impedance | 10 KΩ, 0.5 W |
| Overvoltage Protection | 70 VDC |
| Digital Output | |
| Channels | 2 |
| Type | Isolated Open Collector |
| Sink/Source (NPN/PNP) | Sink |
| Load Voltage | +3.5 ~ +50 VDC |
| Load Current | 700 mA/channel |
| Overvoltage Protection | 60 VDC |
| Overload Protection | 1.4 A |
| Short-circuit Protection | Yes |
| Power on Value | Programmable |
| Safe Value | Programmable |
| COM Ports | |
| Ports | 1 x RS-485 |
| Baud Rate | 1200 ~ 115200 bps |
| Data Format | (N, 8, 1), (N, 8, 2), (O, 8, 1), (E, 8, 1) |
| Protocol | DCON, Modbus RTU, Modbus ASCII |
| Power | |
| Reverse Polarity Protection | Yes |
| Consumption | 1 W max. |
| Powered from Terminal Block | 10 ~ 30 VDC |
| Mechanical | |
| Dimensions (mm) | 52 x 98 x 27 (W x L x H) |
| Installation | DIN-Rail Mounting |
| Environment | |
| Operating Temperature | -25 ~ +75 °C |
| Storage Temperature | -30 ~ +75 °C |
| Humidity | 10 ~ 95% RH, Non-condensing |
Specifications as published by the manufacturer. Subject to change.