Ir para o conteúdo principal Saltar para a pesquisa Saltar para a navegação principal

iSN-101/S2 Liquid Leak Detection Module, 1-ch with Relay Output and RS-485

Informações de produto "iSN-101/S2 Liquid Leak Detection Module, 1-ch with Relay Output and RS-485"

The iSN-101/S2 CR is a standalone 1-channel liquid leak detector that switches its own relay output when liquid is detected, so it can drive local or remote alarms without an additional conversion module. Its RS-485 port supports Modbus RTU and DCON, allowing it to report status to a supervisory system or collection host on the network.

Sensing is handled by a double-core leader cable of up to 500 m, or by point probes at fixed risk locations. Sensitivity is set with a rotary switch across 26 KΩ to 580 KΩ, and the module also raises an audible alarm that can be silenced with a push button. Modbus RTU device addresses can be configured in hardware.

This variant is supplied with a 3 m liquid leak detection cable and a 3 m extended cable. The module is designed for wall mounting and operates from a 10 to 30 VDC supply across -25 to +75 °C.

Applications

  • Water pipe leak monitoring in buildings
  • Detection of leakage from fire pipes and sewage pipes
  • Domestic water, drainage and electrical equipment monitoring
  • Computer room base stations, warehouses, libraries and museums
  • Air handling equipment, refrigeration units, liquid containers and pump tanks
Product type: Liquid leak detection module
Interface: RS-485
Protocol: DCON, Modbus RTU
Relay outputs: 1
Ports: 1
Power input: 10 ~ 30 VDC
Operating temperature: -25 ~ +75 °C
Mounting: Wall mount

Specifications

EMS Protection
EFT (IEC 61000-4-4)±4 kV for Power
ESD (IEC 61000-4-2)±8 kV Air for Random Point
LED Indicators
Status1 as Power Indicator
1 as Alarm Indicator
System
AlarmFor both liquid leak detection and cable-break detection.
BuzzerYes.
Can be muted by a push button.
Relay OutputSignal Relay, Form A x1, SPST
0.25 A @ 250 VAC
0.5 A @ 125 VAC
2 A @ 30 VDC
Liquid Leak Detection
Channels1
Liquid TypeWater, 2uS/cm
Sensor TypeProbe for point detection
or Cable for line detection
Max. Cable Length500 meters
Include Liquid Leak Detection Cable and Extended Cables.
Sensitivity Range26 KΩ ~ 580 KΩ (adjustable by rotary switch)
Cable-break DetectionYes.
For sense cable CA-LLD-DC100X-Lxxx only.
COM Ports
Ports1 x RS-485
Baud RateSoftware Configuration: 1200 ~ 115200 bps
Data Format(N,8,1), (O,8,1), (E,8,1), (N,8,2)
ProtocolModbus RTU or DCON
Power
Reverse Polarity ProtectionYes
Input Range10 ~ 30 VDC
Consumption1.5 W Max.
Mechanical
Dimensions (mm)80 x 70 x 28 (W x L x H)
InstallationWall mount
Environment
Operating Temperature-25 ~ +75 °C
Storage Temperature-30 ~ +80°C
Humidity10 ~ 90% RH, Non-condensing

Specifications as published by the manufacturer. Subject to change.

0 de 0 avaliações

Classificação média de 0 de 5 estrelas

Introduza uma avaliação!

Partilhe as suas experiências com o produto com outros clientes.