The I-7013D CR is a single-channel RTD input module for measuring temperature directly from Pt100, Pt1000 and Ni120 sensors. It supports 2-, 3- and 4-wire RTD connections, and lead resistance elimination is available for 3- and 4-wire wiring, which helps preserve measurement accuracy over longer sensor cable runs.

Local readings appear on a 5-digit 7-segment LED display, while the RS-485 port communicates using the DCON protocol at 1200 to 115200 bps. Open wire detection and a built-in dual watchdog (module and communication) help engineers spot sensor faults and keep unattended installations running. 3000 VDC intra-module isolation separates the input from the rest of the module.

Supplied in a blue cover, the module is designed for DIN-rail mounting and a 10 to 30 VDC supply with reverse polarity protection. It is rated for an operating range of -25 to +75 °C and is typically used in:

  • Building automation
  • Factory automation
  • Machine automation
  • Remote maintenance and diagnosis
  • Testing equipment

Applications

  • Building automation
  • Factory automation
  • Machine automation
  • Remote maintenance
  • Remote diagnosis
  • Testing equipment
Product type: RTD Input Module
Interface: RS-485
Protocol: DCON
Analog inputs: 1
Ports: 1
Isolation: 3000 VDC
Power input: +10 ~ +30 VDC
Operating temperature: -25 ~ +75 °C
Mounting: DIN-rail

Specifications

CPU Module
Watchdog TimerModule, Communication (Programmable)
Display
Type5-Digit 7 Segment LED Display
Isolation
Intra-module Isolation3000 VDC
EMS Protection
EFT (IEC 61000-4-4)±4 kV for Power Line
ESD (IEC 61000-4-2)±2 kV Contact for Each Terminal
Surge (IEC 61000-4-5)±0.5 kV for Power Line
LED Indicators
Status1 x Power and Communication
Analog Input
Channels1
TypeRTD
Sensor TypePt100, Pt1000, Ni120
Resistance Measurement3.2 kΩ max.
Resolution16-bit
Accuracy±0.05% of FSR
Sampling Rate10 Hz
Overvoltage Protection±5 VDC
Open Wire DetectionYes
3-wire RTD Lead Resistance EliminationYes
COM Ports
Ports1 x RS-485
Baud Rate1200 ~ 115200 bps
Data Format(N, 8, 1), (N, 8, 2), (E, 8, 1), or (O, 8, 1)
ProtocolDCON
Power
Reverse Polarity ProtectionYes
Input Range+10 ~ +30 VDC
Consumption1.3 W
Mechanical
Dimensions (mm)72 x 123 x 35 (W x L x H)
InstallationDIN-Rail Mounting
Environment
Operating Temperature-25 ~ +75 °C
Storage Temperature-40 ~ +85 °C
Humidity10 ~ 95% RH, Non-condensing