CAN-2012C CANopen Slave Module, 16-bit 16-ch Analog Input
16-bit CANopen slave analog input module with 8 differential or 16 single-ended channels, supporting CiA 301 v4.02 and CiA 401 v2.1 with a default EDS file.
- CANopen NMT slave with Node Guarding and Heartbeat error control
- 8 differential or 16 single-ended analog inputs, software selectable
- 16-bit resolution, ±0.1% FSR accuracy and 4000 samples/s total sampling rate
- Voltage and current input ranges including 4~20mA
- Supports CiA 301 v4.02 and CiA 401 v2.1, with a default EDS file
- Passed the CiA CANopen conformance test tool validation
308,00 € per piece
| 1–9 pcs | 308,00 € | |
|---|---|---|
| 10–30 pcs | 299,00 € | −3 % |
| 31+ pcs | 293,00 € | −5 % |
Informações de produto "CAN-2012C CANopen Slave Module, 16-bit 16-ch Analog Input"
The CAN-2012C is a CANopen slave analog input module that brings 16-bit measurements onto a CAN bus network. It provides 8 differential or 16 single-ended inputs, selectable in software, and covers voltage ranges of ±10V, ±5V, ±2.5V and 0~10V as well as current ranges of ±20mA, 0~20mA and 4~20mA. Each channel can be configured individually.
Built for CANopen networks, the module follows CiA 301 v4.02 and CiA 401 v2.1 and operates as an NMT slave with Node Guarding and Heartbeat error control. A default EDS file is provided for use with standard CANopen master software, and the module has passed the CiA CANopen conformance test tool, which simplifies commissioning with masters from ICP DAS or other manufacturers.
Electrical features include 4 kV contact ESD protection on each channel, support for a 10 to 30 VDC supply, and isolation rated at 2500 Vrms for photo-coupling and 3000 VDC for DC-to-DC. The module mounts on DIN-rail and operates from -25 to +75 °C.
Applications
- Industrial machinery control
- Factory automation
- Packaging machine control
- Remote data acquisition
- Environmental monitoring
- Vehicle control systems
- Medical equipment control
| Product type: | Fieldbus I/O module |
|---|---|
| Interface: | CAN bus |
| Protocol: | CANopen |
| Analog inputs: | 8 diff / 16 single-ended |
| Isolation: | 2500 Vrms |
| Power input: | 10 ~ 30 VDC |
| Operating temperature: | -25 ~ +75 °C |
| Mounting: | DIN-rail |
Specifications
| CPU Module | |
|---|---|
| Watchdog Timer | Hardware watchdog |
| LED Indicators | |
| Status | 3 LEDs to PWR, RUN and ERR |
| Analog Input | |
| Channels | 8 Differential or 16 Single-ended (Software Selectable) |
| Sensor Type | ±10V, ±5V, ±2.5V, 0~10V, ±20mA, 0~20mA,4~20mA |
| Resolution | 16-bit |
| Accuracy | +/-0.1% FSR |
| Sampling Rate | 4000 Samples/Sec. (Total) |
| Input Impedance | ≥ 1 MΩ |
| Common Mode Rejection | 84 dB |
| Overvoltage Protection | 70 Vrms |
| Individual Channel Configuration | Yes |
| Zero Drift | ±0.2 μV/ °C |
| Span Drift | ±5 ppm/ °C |
| CANopen | |
| Baud Rate | 10 k ~ 1 M |
| Isolation | 3000 VDC for DC-to-DC, 2500 Vrms for photo-couple |
| Terminal Resistor | Built-in 120Ω |
| Protocol | CiA 301 v4.02, CiA 401 v2.1 |
| Node ID | 1 ~ 99 |
| No. of PDOs | 10 RxPDO , 10 TxPDO |
| PDO Mode | Event Triggered, Remotely requested, Cyclic and acyclic SYNC |
| Error Control | Node Guarding protocol / Heartbeat Producer |
| NMT | Slave |
| EMCY Message | Yes |
| Power | |
| Consumption | 0.5 W |
| Mechanical | |
| Dimensions (mm) | 33 x 99 x 78 ( W x L x H ) |
| Installation | DIN-Rail |
| Environment | |
| Operating Temperature | -25 ~ +75 °C |
| Storage Temperature | -30 ~ +80 °C |
| Humidity | 10 ~ 90% RH, Non-condensing |
Specifications as published by the manufacturer. Subject to change.