PM-3033-MTCP 3-Phase Power Meter, Modbus TCP, 1A/5A CT Input
DIN-rail three-phase power meter with Modbus TCP over Ethernet, direct 1A/5A secondary CT input, true RMS measurements and bi-directional energy readings.
- Modbus TCP over a 10/100 Base-TX RJ45 port, with PoE support
- Direct input of secondary side 1A/5A CT, no dedicated CTs required
- True RMS voltage, current, power, energy and power factor measurement
- Bi-directional energy measurement
- Energy analysis for 3P4W, 3P3W, 1P3W and 1P2W wiring
- Voltage input up to 500 V; W accuracy better than 0.5% (PF=1; input current >0.5 A)
€ 271,00 per piece
| 1–9 pcs | € 271,00 | |
|---|---|---|
| 10–30 pcs | € 263,00 | −3 % |
| 31+ pcs | € 257,00 | −5 % |
Productinformatie "PM-3033-MTCP 3-Phase Power Meter, Modbus TCP, 1A/5A CT Input"
The PM-3033-MTCP is a DIN-rail three-phase power meter that reports true RMS voltage, current and power values over Modbus TCP through a single RJ45 port. It accepts secondary 1A or 5A current transformer inputs directly, so dedicated CTs are not needed when metering existing installations.
It supports energy analysis for 3P4W, 3P3W, 1P3W and 1P2W wiring, with voltage inputs from 10 to 500 V at 50/60 Hz. Active, reactive and apparent power and energy are available, together with power factor, frequency and total harmonic distortion (THD). Power accuracy is better than 0.5% at PF=1 with input current above 0.5 A, and data is updated every second.
The meter operates from a +12 ~ 48 VDC supply over a -20 ~ +70 °C range and is listed for CE, UKCA, FCC, RoHS and WEEE, with IEC 61010-1 and EN 61010-1 safety standards cited in the source data. Its plastic casing and DIN-rail mounting suit switchgear and generator monitoring panels.
Applications
- Generator monitoring
- Switchgear distribution systems
- Energy management
| Product type: | Power meter |
|---|---|
| Interface: | Ethernet |
| Protocol: | Modbus TCP |
| Ports: | 1 |
| PoE: | Yes |
| Power input: | +12 ~ 48 VDC |
| Operating temperature: | -20 ~ +70 °C |
| Mounting: | DIN-rail |
| Housing: | Plastic |
Specifications
| AC Power Measurement | |
|---|---|
| Wiring | 3P4W-3CT, 3P3W-2CT, 3P3W-3CT, 1P2W-1CT, 1P3W-2CT |
| Loops | 3-phase: 1 1-phase: 3 @ 1P2W-1CT 1 @ 1P3W-2CT |
| Input Voltage | 10 ~ 500 V |
| Input Current | 0.05 A ~ 5 A |
| Input Frequency | 50/60 Hz |
| W Accuracy | Better than 0.5% (PF=1; Input Current >0.5A) |
| Power Parameter Measurement | True RMS voltage (Vrms), True RMS current (Irms), Active Power (kW), Active Energy (kWh), Apparent Power (kVA), Apparent Energy (kVAh), Reactive Power (kVAR), Reactive Energy (kVARh), Power Factor (PF), Frequency |
| Data Update Rate | 1 Second |
| Ethernet | |
| Ports | 1x RJ45, 10/100 Base-TX |
| PoE | Yes |
| Protocol | Modbus TCP |
| Power | |
| Input Range | +12 ~ 48 VDC |
| Consumption | 2W |
| Mechanical | |
| Casing | Plastic |
| Dimensions (mm) | 33 x 127 x 100 (W x L x H) |
| Installation | DIN-Rail Mounting |
| Environment | |
| Operating Temperature | -20 ~ +70 °C |
| Storage Temperature | -25 ~ +80 °C |
| Humidity | 10 ~ 90% RH, Non-condensing |
Specifications as published by the manufacturer. Subject to change.
Aanmelden