Ga naar de hoofdinhoud Ga naar de zoekopdracht Ga naar de hoofdnavigatie

I-2533CS-FD CAN/CAN FD to Single-mode Fibre Bridge, 30 km, SC Connector

Productinformatie "I-2533CS-FD CAN/CAN FD to Single-mode Fibre Bridge, 30 km, SC Connector"

The I-2533CS-FD bridges two CAN or CAN FD networks over single-mode fibre. It converts the electrical CAN/CAN FD signal to optical transmission, so the physical length of a CAN segment is no longer limited by copper cabling. It is a practical choice where a CAN bus must span a site, a building or a distance beyond the reach of standard bus wiring.

Each network runs at its own bit rate, so the two sides can operate with different CAN or CAN FD baud rates. A bus error on one network does not disrupt the other, which helps keep faults contained. Basic CAN message routing is available through Group ID settings, and message filtering can be configured on the CAN side.

The unit mounts on a DIN-rail and is powered from +10 VDC to +30 VDC. Status LEDs show power, CAN activity and fibre status, and fibre broken-line detection is included. Firmware can be updated over USB.

Applications

  • Linking two CAN or CAN FD bus networks over long single-mode fibre runs
  • Extending CAN bus segments beyond the distance limits of electrical cabling
  • Isolating bus faults between separate CAN networks
  • Connecting CAN networks that operate at different bit rates
Product type: CAN/CAN FD fibre bridge
Interface: CAN/CAN FD, single-mode fibre (SC)
Protocol: CAN 2.0 A/B, CAN FD
Ports: 1
Power input: +10 ~ +30 VDC
Operating temperature: -25 ~ +75 °C
Mounting: DIN-rail
Housing: Plastic

Specifications

LED Indicators
Status1 x Power, 3 x CAN status, 2 x Fiber status
Fiber
Fiber Cable8.3/125, 8.7/125, 9/125 or 10/125 μm
Wavelength1310 nm
TX Output-15 dBm Min. , -8 dBm Max.
Transmission Distance30 km (9/125 μm recommended)
RX Sensitivity-34 dBm Max.
RX Overload-5 dBm Max.
Budget19 dBm
Propagation Delay190 us (*Note1)
USB
SpecificationUSB 2.0 High Speed (480Mbps)
ConnectorUSB Type B, Mini-B
DriverBuilt-in Windows 7/8.1/10
CAN
Ports1
SpecificationISO 11898-2, CAN 2.0 A/B and FD
Baud RateCAN bit rates: 10 k ~ 1 M bps,
CAN FD bit rates for data field: 100 k ~ 10M bps (*Note2)
Terminal ResistorSwitch for 120Ω terminal resistor
FilterYes
Power
Input Range+10 VDC ~ +30 VDC
Consumption3 W
Mechanical
CasingPlastic
Dimensions (mm)33 x 127 x 101 (W x L x H)
InstallationDIN-Rail
Environment
Operating Temperature-25 ~ +75 °C
Storage Temperature-30 ~ +80 °C
Humidity10 ~ 90% RH, Non-condensing

Specifications as published by the manufacturer. Subject to change.

0 van 0 beoordelingen

Gemiddelde waardering van 0 van 5 sterren

Geef een beoordeling