DNM-831I-600V-2000A Voltage/Current Input Module, 600 V and 2000 A
Single-channel voltage attenuator and clip-on current transformer that scales ±600 V and ±2000 A inputs to ±10 V outputs, with 3000 VDC isolation for DIN-rail installations.
- Measures up to ±600 V and up to ±2000 A on one voltage channel and one current channel
- Linear attenuation to ±10 V outputs for use with analogue input modules
- 3000 VDC intra-module and channel-to-channel isolation
- High input impedance and straightforward wiring
- Clip-type current transformer with Φ40.5 mm inside diameter and 1.5 m leading cable
- Metal casing with DIN-rail mounting, operating range -25 ~ +75 °C
262,00 € per piece
| 1–9 pcs | 262,00 € | |
|---|---|---|
| 10–30 pcs | 255,00 € | −3 % |
| 31+ pcs | 249,00 € | −5 % |
Info sui prodotti "DNM-831I-600V-2000A Voltage/Current Input Module, 600 V and 2000 A"
The DNM-831I-600V-2000A lets engineers bring high DC and AC voltage and high current signals into standard analogue input hardware. One channel attenuates voltage up to ±600 V and another channel, using a clip-on current transformer, handles up to ±2000 A. Both paths deliver a ±10 V output that suits common analogue input modules.
Isolation is provided between the inputs and outputs and between channels, with 3000 VDC for both, which helps keep noise from the high-power side out of the measurement signal. The metal housing mounts on a DIN rail and is powered from +10 VDC to +30 VDC.
Typical use is in monitoring and measurement systems where the primary current or voltage is too high for direct connection to an analogue input. The current transformer is supplied with a 1.5 m leading cable and the CA-040415-1 cable is included in this ordering code.
Applications
- High-current measurement with analogue input modules
- High-voltage AC/DC voltage monitoring
- Signal conditioning in industrial measurement systems
| Product type: | Voltage attenuator and current transformer |
|---|---|
| Isolation: | 3000 VDC |
| Power input: | +10 ~ +30 VDC |
| Operating temperature: | -25 ~ +75 °C |
| Mounting: | DIN-rail |
| Housing: | Metal |
Specifications
| EMS Protection | |
|---|---|
| ESD (IEC 61000-4-2) | ±4 kV contact for power line, input and output channels, ±8 kV air for random point |
| Surge (IEC 61000-4-5) | ±3 kV for power liner |
| CT | |
| Type | Clip |
| Inside Diameter | Φ40.5 mm |
| Leading Cable | 1.5 m |
| Analog Input | |
| Channels | High Current: 1 High Voltage: 1 |
| Type | AC/DC Current AC/DC Voltage |
| Range | High Current: ±2000 A High Voltage: ±600 VDC |
| Accuracy | High Current: 1% of FSR High Voltage: 1% of FSR |
| Bandwidth | High Current: 0 ~ 50 KHz High Voltage: 20 Hz ~ 20 kHz |
| Isolation | High Current: 2.5 KV @ 50 (60) HZ/1 min |
| Analog Output | |
| Channels | High Current: 1 High Voltage: 1 |
| Type | AC/DC Current AC/DC Voltage |
| Range | • High Current: ±10 VDC or 10 VAC • High Voltage: ±10 VDC or 10 VAC |
| Power | |
| Input Range | +10 VDC ~ +30 VDC |
| Consumption | 1.8 W |
| Mechanical | |
| Casing | Metal |
| Dimensions (mm) | 103 x 97 x 29 (W x L x D) |
| Installation | DIN-Rail Mounting |
| Environment | |
| Operating Temperature | -25 ~ +75 °C |
| Storage Temperature | -30 ~ +75 °C |
| Humidity | 10 ~ 90% RH, Non-condensing |
Specifications as published by the manufacturer. Subject to change.