The FR-2017iT CR is an FRnet analog input module for remote measurement, combining 12-bit conversion on 8 differential or 16 single-ended channels. Channel mode is switch selectable, and the module accepts a range of voltage and current signals, from ±150 mV up to ±10 V and ±20 mA, plus 0 ~ 20 mA and 4 ~ 20 mA. Each input range can be applied to all channels through switch settings, or set per channel in software when the optional CA-0904 cable is fitted.

Each analog input is protected against high voltage, with overvoltage ratings of 240 Vrms for differential and 150 Vrms for single-ended inputs. The module provides 3000 Vrms intra-module isolation and an isolated communication line, and the FRnet interface uses wire-saving 2-wire twisted-pair cabling with 250 kbps or 1 Mbps transfer speeds selectable by DIP switch.

FR-2000 modules can be daisy chained on FRnet to extend remote I/O control from a PC, PAC or PLC. The module is a DIN-rail mounted plastic unit powered from +10 VDC to +30 VDC and rated for operation from -25 ~ +75 °C.

Applications

  • Remote analog signal acquisition on FRnet networks
  • Extending remote I/O control from PC, PAC or PLC systems
  • Measurement of process voltage and current signals in noisy or high-voltage environments
Product type: Analog Input Module
Interface: FRnet
Analog inputs: 8 differential / 16 single-ended
Isolation: 3000 Vrms
Power input: +10 VDC ~ +30 VDC
Operating temperature: -25 ~ +75 °C
Mounting: DIN-rail
Housing: Plastic

Specifications

Isolation
Intra-module Isolation3000 Vrms
EMS Protection
EFT (IEC 61000-4-4)±4 kV contact for power liner
ESD (IEC 61000-4-2)±4 kV contact for power liner, communication line and each channel
±8 kV air for random point
Surge (IEC 61000-4-5)± 3 kV for power liner
LED Indicators
StatusPower, Communication Run, Communication Error, Terminal Resistor, Analog Input
Analog Input
Channels8 differential or 16 single-ended, switch selectable
TypeVoltage
Current
Range±150 mV, ±500 mV, ±1 V, ±5 V, ±10 V
±20 mA, 0 ~ 20 mA, 4 ~ 20 mA (requires optional external 125 Ω resistor for current input)
Resolution16-bit (1 channel)/12-bit (8/16 channels)
Accuracy±0.1% (1 channel)/±0.5% (8/16 channels) or better
Sampling Rate10 samples/second (1 channel)/50 samples/second (8/16 channels) total
Bandwidth15.7 Hz (1 channel)/78.7Hz (8/16 channels)
Input ImpedanceVoltage: 2 MΩ (Differential), 1 MΩ (Single-ended)
Common Mode Rejection86 dB Min.
Normal Mode Rejection100 dB
Overvoltage ProtectionDifferential: 240 Vrms, Single-ended: 150 Vrms
Individual Channel ConfigurationYes (by software, requires optional CA-0904 cable)
Zero Drift±20 uV/°C
Span Drift±25 ppm/°C
FRnet
Wire CableBelden 9841 (2P twisted-pair cable),
When different cables are used, the transmission distance may be changed
Transfer Speed250 kbps and 1Mbps (Default)
DIP Switch Selectable
Transfer DistanceMax. 400 m for speed 250 K
Max. 100 m for speed 1M (Default)
Cyclic Time2.88 ms for speed 250 K
0.72 ms for speed 1 M (Default)
Power
Input Range+10 VDC ~ +30 VDC (Non-isolated)
Consumption2.4 W Max.
Mechanical
CasingPlastic
Dimensions (mm)33 x 102 x 107 (W x L x H)
InstallationDIN-Rail Mounting
Environment
Operating Temperature-25 ~ +75 °C
Storage Temperature-30 ~ +85 °C
Humidity10 ~ 90% RH, Non-condensing

Specifications as published by the manufacturer. Subject to change.