tM-C8 8-Channel Isolated Digital Output Module, Sink (NPN), RS-485
8-channel isolated sink-type (NPN) digital output module with an RS-485 port supporting DCON, Modbus RTU and Modbus ASCII. DIN-rail mounted.
- Eight isolated open-collector digital outputs, sink (NPN) type
- Load voltage +3.5 ~ +50 VDC with 700 mA per channel
- Programmable power-on value and safe value for each output
- Short-circuit protection with 60 VDC overvoltage protection
- Dual watchdog for module and communication
- 3750 VDC intra-module isolation and 4 kV ESD contact protection
106,00 € per piece
| 1–9 pcs | 106,00 € | |
|---|---|---|
| 10–30 pcs | 102,00 € | −4 % |
| 31+ pcs | 100,00 € | −6 % |
Informacije o proizvodu "tM-C8 8-Channel Isolated Digital Output Module, Sink (NPN), RS-485"
The tM-C8 CR is an RS-485 remote I/O module that switches eight isolated open-collector outputs in sink (NPN) mode. Each channel is photocoupler-isolated and protected against short circuits, so it suits on/off control tasks where output reliability matters.
Power-on and safe output states are both programmable, so outputs can be held in a defined condition when the module starts up or when communication is lost. A dual watchdog, covering the module and the communication link, adds further protection for unattended operation.
Electrical robustness is covered by 3750 VDC intra-module isolation and 4 kV ESD contact protection on each terminal. The module draws up to 0.8 W from a 10 ~ 30 VDC terminal block supply and is designed for DIN-rail installation.
Applications
- On/off control
- Industrial automation
- Industrial machinery
- Building automation
- Food and beverage systems
- Semiconductor fabrication
- Control systems
| Product type: | Digital output module |
|---|---|
| Interface: | RS-485 |
| Protocol: | DCON, Modbus ASCII, Modbus RTU |
| Digital outputs: | 8 |
| Ports: | 1 |
| Isolation: | 3750 VDC |
| Power input: | 10 ~ 30 VDC |
| Operating temperature: | -25 ~ +75 °C |
| Mounting: | DIN-rail |
Specifications
| CPU Module | |
|---|---|
| Watchdog Timer | Module, Communication (Programmable) |
| Isolation | |
| Intra-module Isolation | 3750 VDC |
| EMS Protection | |
| EFT (IEC 61000-4-4) | ±4 kV for Power |
| ESD (IEC 61000-4-2) | ±4 kV Contact for Each Terminal ±8 kV Air for Random Point |
| LED Indicators | |
| Status | 1 x Power and Communication |
| Digital Output | |
| Channels | 8 |
| Type | Isolated Open Collector |
| Sink/Source (NPN/PNP) | Sink |
| Load Voltage | +3.5 ~ +50 VDC |
| Load Current | 700 mA/channel |
| Overvoltage Protection | 60 VDC |
| Overload Protection | 1.4 A |
| Short-circuit Protection | Yes |
| Power on Value | Programmable |
| Safe Value | Programmable |
| COM Ports | |
| Ports | 1 x RS-485 |
| Baud Rate | 1200 ~ 115200 bps |
| Data Format | (N, 8, 1), (N, 8, 2), (O, 8, 1), (E, 8, 1) |
| Protocol | DCON, Modbus RTU, Modbus ASCII |
| Power | |
| Reverse Polarity Protection | Yes |
| Consumption | 0.8 W max. |
| Powered from Terminal Block | 10 ~ 30 VDC |
| Mechanical | |
| Dimensions (mm) | 52 x 98 x 27 (W x L x H) |
| Installation | DIN-Rail Mounting |
| Environment | |
| Operating Temperature | -25 ~ +75 °C |
| Storage Temperature | -30 ~ +75 °C |
| Humidity | 10 ~ 95% RH, Non-condensing |
Specifications as published by the manufacturer. Subject to change.