M-7018R-G 8-ch Thermocouple Input Module, 240 Vrms Overvoltage Protection
8-channel differential analog input module for thermocouple, voltage and current signals, with 240 Vrms overvoltage protection and RS-485 Modbus RTU or DCON communication.
- Eight differential analog inputs for thermocouple, voltage and current signals
- Thermocouple types J, K, T, E, R, S, B, N and C, with software selectable open wire detection
- 240 Vrms overvoltage protection and 200 VDC common voltage protection
- 3000 VDC intra-module isolation and ±4 kV ESD contact protection on each terminal
- 16-bit resolution with ±0.1% of FSR accuracy and 10 Hz total sampling rate
- 1 x RS-485 port supporting Modbus RTU or DCON at 1200 ~ 115200 bps
273,00 € per piece
| 1–9 pcs | 273,00 € | |
|---|---|---|
| 10–30 pcs | 264,00 € | −3 % |
| 31+ pcs | 259,00 € | −5 % |
Informacije o proizvodu "M-7018R-G 8-ch Thermocouple Input Module, 240 Vrms Overvoltage Protection"
The M-7018R-G is an RS-485 analog input module with eight differential channels for thermocouple, voltage and current measurement. It suits engineers who need to read temperature sensors and process signals on a networked DIN-rail module, with the option of Modbus RTU or DCON selected in software.
Why choose the M-7018R-G: The R variant adds a high level of input protection, with overvoltage tolerance up to 240 Vrms and 200 VDC common voltage protection. Open wire detection for thermocouple channels is software selectable, which helps identify broken sensor wiring. The gray-cover version is the ordering option covered by this listing.
Channels can be configured individually, and the module provides 3000 VDC isolation between internal circuits, 4 kV ESD protection on each terminal and a built-in dual watchdog for module and communication monitoring. It is rated for operation from -25 ~ +75 °C.
Applications
- Building Automation
- Factory Automation
- Machine Automation
- Remote Maintenance
- Remote Diagnosis
- Testing Equipment
| Product type: | Analog Input Module |
|---|---|
| Interface: | RS-485 |
| Protocol: | DCON, Modbus RTU |
| Analog inputs: | 8 |
| Ports: | 1 |
| Isolation: | 3000 VDC |
| Power input: | +10 ~ +30 VDC |
| Operating temperature: | -25 ~ +75 °C |
| Mounting: | DIN-rail |
| Housing: | Gray |
Specifications
| CPU Module | |
|---|---|
| Watchdog Timer | Module, Communication (Programmable) |
| Isolation | |
| Intra-module Isolation | 3000 VDC |
| EMS Protection | |
| EFT (IEC 61000-4-4) | ±4 kV for Power Line |
| ESD (IEC 61000-4-2) | ±4 kV Contact for Each Terminal |
| Surge (IEC 61000-4-5) | ±0.5 kV for Power Line |
| LED Indicators | |
| Status | 1 x Power and Communication |
| Analog Input | |
| Channels | 8 Differential |
| Type | Voltage Current Thermocouple |
| Sensor Type | Thermocouple: J, K, T, E, R, S, B, N, C |
| Range | Voltage: ±15 mV, ±50 mV, ±100 mV, ±500 mV, ±1 V, ±2.5 V Current: ±20 mA, 0 ~ +20 mA, +4 ~ +20 mA (requires an optional external 125 Ω resistor) |
| Resolution | 16-bit |
| Accuracy | ±0.1% of FSR |
| Sampling Rate | 10 Hz (Total) |
| Input Impedance | > 400 kΩ |
| Common Voltage Protection | 200 VDC |
| Overvoltage Protection | 240 Vrms |
| Overcurrent Protection | Yes |
| Individual Channel Configuration | Yes (*Note1) |
| Open Wire Detection | For Thermocouple Only (Software Selectable, *Note2) |
| COM Ports | |
| Ports | 1 x RS-485 |
| Baud Rate | 1200 ~ 115200 bps |
| Data Format | (N, 8, 1), (N, 8, 2), (E, 8, 1), or (O, 8, 1) |
| Protocol | Modbus RTU, DCON |
| Power | |
| Reverse Polarity Protection | Yes |
| Input Range | +10 ~ +30 VDC |
| Consumption | 1.0 W |
| Mechanical | |
| Dimensions (mm) | 72 x 123 x 35 (W x L x H) |
| Installation | DIN-Rail Mounting |
| Environment | |
| Operating Temperature | -25 ~ +75 °C |
| Storage Temperature | -40 ~ +85 °C |
| Humidity | 10 ~ 95% RH, Non-condensing |
Specifications as published by the manufacturer. Subject to change.