Siirry pääsisältöön Siirry hakuun Siirry päänavigointiin

tSL-PA4R1 Stack Light Monitoring Module, 4-ch AC DI with Relay Output

Tuotetiedot "tSL-PA4R1 Stack Light Monitoring Module, 4-ch AC DI with Relay Output"

Monitor machine status without touching the control logic. The tSL-PA4R1 reads the indicator outputs of a machine's stack light and reports the state of each colour segment as ON, OFF or flashing. It is intended for MES-connected machines, where it helps teams track operating stages and machine utilisation through SCADA software without interfering with the equipment itself.

Beyond single-segment detection, the module can be configured to recognise user-defined combinations of several colour segments and reports how long the previous status lasted. Status data is available over Modbus RTU, Modbus TCP and MQTT, using either the RS-485 or Ethernet interface.

Power can come from PoE (IEEE 802.3af, Class 1) or a DC terminal block (+10 ~ +48 VDC), giving redundant supply options. Configuration is handled through a built-in web interface, which also supports firmware updates over Ethernet. A relay output allows an alarm device to be driven directly.

Applications

  • Factory automation
  • Machine automation
  • Remote maintenance
  • Remote diagnosis
  • Testing equipment
Product type: Stack light monitor
Interface: Ethernet, RS-485
Protocol: Modbus RTU, Modbus TCP, MQTT
Digital inputs: 4
Relay outputs: 1
Ports: 1
PoE: IEEE 802.3af, Class 1
Isolation: 3750 VDC
Power input: +10 ~ +48 VDC, PoE
Operating temperature: -25 ~ +75 °C
Mounting: DIN-rail

Specifications

Software
Built-in Web ServerYes
CPU Module
Watchdog TimerYes, Module (2.3 seconds), Communication (Programmable)
System
SecurityIP filter (whitelist) and Password (web)
Isolation
Intra-module Isolation3750 VDC
EMS Protection
EFT (IEC 61000-4-4)±2 kV for Power
ESD (IEC 61000-4-2)±4 kV Contact for Each Terminal
±8 kV Air for Random Point
LED Indicators
StatusS1: System indicator
E1: PoE indicator (Green)
Link/Act (Yellow)
Digital Input
Able to detect the status of each color segment: ON, OFF, or FlashingYes
Digital Input
Channels4
TypeWet Contact
Sink/Source (NPN/PNP)Sink/Source
ON Voltage Level80 VAC ~240 VAC
OFF Voltage Level30 VAC Max.
Isolation3750 VDC
Input Impedance150 KΩ, 2 W
Overvoltage Protection300 VAC
Low Pass Filter0 ~ 6500 ms, programmable
Max. Stack Light Flashing Speed60 Hz
Report Duration of Previous StatusYes, 10 ~ 65500 ms
Status monitoring for user-defined combinations of multiple color segmentsMax. 81 combinations
Relay Output
Channels1
TypePower Relay, Form A (SPST N.O.)
Contact Rating5 A @ 250 VAC or 5 A @ 30 VDC
Operate Time6 ms
Release Time3 ms
Electrical EnduranceVDE:
5 A @ 250 VAC 30,000 ops (10 ops/minute) at 75°C
5 A @ 30 VDC 70,000 ops (10 ops/minute) at 75°C
UL:
5 A @ 250 VAC/30 VDC 6,000 ops
3 A @ 250 VAC/30 VDC 100,000 ops
Mechanical Endurance20,000,000 ops at no load (300 ops/minute)
Power on ValueYes, Programmable
Safe ValueYes, Programmable
Ethernet
Ports10/100 Base-TX, 8-Pin RJ-45 x1 (Auto-negotiating, Auto-MDI/MDIX, LED indicators)
COM Ports
Baud Rate1200 ~ 115200 bps
ProtocolModbus/RTU, Modbus TCP and MQTT
Power
Reverse Polarity ProtectionYes
Input RangeTerminal Block: +10 ~ +48 VDC
PoE: IEEE 802.3af, Class 1
ConsumptionPoE: 1 W Max.
Non-PoE: 0.9 W Max.
Mechanical
Dimensions (mm)52 x 98 x 27 (W x L x H)
InstallationDIN-Rail Mounting
Environment
Operating Temperature-25 ~ +75 °C
Storage Temperature-30 ~ +80°C
Humidity10 ~ 95% RH, Non-condensing

Specifications as published by the manufacturer. Subject to change.

0 / 0 arvostelua

Keskimääräinen arvosana 0 5 tähdestä

Jätä arvostelu!

Jaa kokemuksesi muiden asiakkaiden kanssa.