M-7017mC-16-G Current Input Module, 16-ch Data Logger, DCON/Modbus RTU
16-channel current input module with 16-bit resolution, built-in measurement resistors and a data logger holding up to 100,000 records. Supports DCON and Modbus RTU over RS-485.
- 16 current input channels, each with a built-in resistor for direct current measurement
- Jumper-selectable differential or single-ended wiring
- 16-bit resolution with selectable Normal (10 Hz) or Fast (200 Hz) sampling
- Open wire detection for 4 ~ 20 mA inputs
- Data logger storing up to 100,000 timestamped records from 16 channels
- Modbus RTU and DCON over one RS-485 port at 1200 ~ 115200 bps
360,00 € per piece
| 1–9 pcs | 360,00 € | |
|---|---|---|
| 10–30 pcs | 349,00 € | −3 % |
| 31+ pcs | 342,00 € | −5 % |
Tuotetiedot "M-7017mC-16-G Current Input Module, 16-ch Data Logger, DCON/Modbus RTU"
M-7017mC-16-G CR is a 16-channel current-only analogue input module for RS-485 networks. Its built-in resistors allow 0 ~ 20 mA, 4 ~ 20 mA and ±20 mA signals to be measured directly, without an external shunt resistor to fit and match.
Each channel can be wired as differential or single-ended via jumper selection, and the sampling rate can be set to Normal Mode (10 Hz) or Fast Mode (200 Hz). Open wire detection covers 4 ~ 20 mA inputs, and the module provides 3000 VDC intra-module isolation along with 4 kV ESD and 110 VDC overvoltage protection on the current inputs.
The onboard data logger records readings from all 16 channels with date and time stamps, storing up to 100,000 records for later download. The LogReader utility reads this log and exports it to CSV. The gray-cover variant is supplied with CE, UKCA, FCC, RoHS and WEEE certification.
Applications
- Building Automation
- Factory Automation
- Machine Automation
- Remote Maintenance
- Remote Diagnosis
- Testing Equipment
| Product type: | Current Input Module |
|---|---|
| Interface: | RS-485 |
| Protocol: | DCON, Modbus RTU |
| Analog inputs: | 16 |
| Ports: | 1 |
| Isolation: | 3000 VDC |
| Power input: | +10 ~ +48 VDC |
| Operating temperature: | -25 ~ +75 °C |
| Mounting: | DIN-rail |
| Housing: | Gray cover |
Specifications
| Data Logger | |
|---|---|
| Max. Records | Up to 100,000 records from 16 current input channels |
| CPU Module | |
| Real Time Clock | Yes |
| Watchdog Timer | Module, Communication (Programmable) |
| Isolation | |
| Intra-module Isolation | 3000 VDC |
| EMS Protection | |
| EFT (IEC 61000-4-4) | ±4 kV for Power Line |
| ESD (IEC 61000-4-2) | ±4 kV Contact for Each Terminal |
| Surge (IEC 61000-4-5) | ±2 kV for Power Line |
| LED Indicators | |
| Status | 1 x Power and Communication |
| Analog Input | |
| Channels | 16 Differential or Single-ended Wiring (Jumper Selectable) |
| Range | ±20 mA, 0 ~ 20 mA, 4 ~ 20 mA |
| Resolution | 16-bit |
| Accuracy | Normal Mode: ±0.1% of FSR Fast Mode: ±0.2 % of FSR |
| Sampling Rate | Normal Mode: 10 Hz Fast Mode: 200 Hz |
| Common Voltage Protection | 25 VDC |
| Overvoltage Protection | 110 VDC |
| Overcurrent Protection | 50 mA at 110 VDC |
| Individual Channel Configuration | Yes |
| Open Wire Detection | For 4 ~ 20 mA Only |
| COM Ports | |
| Ports | 1 x RS-485 |
| Baud Rate | 1200 ~ 115200 bps |
| Data Format | (N, 8, 1), (N, 8, 2), (E, 8, 1), or (O, 8, 1) |
| Protocol | Modbus RTU, DCON |
| Power | |
| Reverse Polarity Protection | Yes |
| Input Range | +10 ~ +48 VDC |
| Consumption | 0.6 W |
| Mechanical | |
| Dimensions (mm) | 76 x 121 x 42 (W x L x H) |
| Installation | DIN-Rail Mounting |
| Environment | |
| Operating Temperature | -25 ~ +75 °C |
| Storage Temperature | -40 ~ +85 °C |
| Humidity | 10 ~ 95% RH, Non-condensing |
Specifications as published by the manufacturer. Subject to change.