DN-831I-100V-50A Voltage Attenuator and Current Transformer, 1-ch
Signal conditioning module that scales ±100 V DC voltage and ±50 A current to ±10 V outputs for analog input modules, with 3000 VDC isolation.
- Measures up to ±100 V and ±50 A on one voltage and one current channel
- Outputs scaled to ±10 V for analog input modules such as I-7017 and I-87017
- 3000 VDC intra-module and channel-to-channel isolation
- Linear attenuation ratio with high input impedance
- Clip-on current transformer, Φ21 mm aperture, 1.5 m lead, with CA-040415 cable included
- Power input +10 VDC to +30 VDC, 1.8 W consumption
140,00 € per piece
| 1–9 pcs | 140,00 € | |
|---|---|---|
| 10–30 pcs | 136,00 € | −3 % |
| 31+ pcs | 133,00 € | −5 % |
Πληροφορίες για το προϊόν "DN-831I-100V-50A Voltage Attenuator and Current Transformer, 1-ch"
DN-831I-100V-50A is a DIN-rail signal conditioner that brings one high voltage input and one high current input into the measurement range of standard analog input modules. The voltage channel attenuates ±100 V to ±10 V, and the current channel uses a clip-on current transformer to scale ±50 A to ±10 V.
Each channel is isolated from the other and from the module's inputs and outputs, with 3000 VDC isolation between modules and between channels. This helps keep noise from the high-power side out of the measurement signal. The attenuation ratio is linear and the input impedance is high.
The CR ordering code includes the CA-040415 cable and the ASO-0002 current transformer, so the clip-on CT with its 1.5 m lead and Φ21 mm aperture is supplied with the unit. It runs from a +10 VDC to +30 VDC supply, draws 1.8 W, and is rated for -25 ~ +75 °C operation.
Applications
- High current measurement with analog input modules
- High voltage DC and AC measurement with analog input modules
| Product type: | Signal conditioning module |
|---|---|
| Analog inputs: | 2 |
| Analog outputs: | 2 |
| Isolation: | 3000 VDC |
| Power input: | +10 ~ +30 VDC |
| Operating temperature: | -25 ~ +75 °C |
| Mounting: | DIN-rail |
| Housing: | Plastic |
Specifications
| EMS Protection | |
|---|---|
| ESD (IEC 61000-4-2) | ±4 kV contact for power line, input and output channels, ±8 kV air for random point |
| Surge (IEC 61000-4-5) | ±3 kV for power liner |
| CT | |
| Type | Clip |
| Inside Diameter | Φ21 mm |
| Leading Cable | 1.5 m |
| Analog Input | |
| Channels | High Current: 1 High Voltage: 1 |
| Type | AC/DC Current AC/DC Voltage |
| Range | High Current: ±50 A High Voltage: ±100 VDC |
| Accuracy | High Current: 1% of FSR High Voltage: 1% of FSR |
| Bandwidth | High Current: 0 ~ 50 KHz High Voltage: 20 Hz ~ 20 kHz |
| Isolation | High Current: 2.5 KV @ 50 (60) HZ/1 min |
| Analog Output | |
| Channels | High Current: 1 High Voltage: 1 |
| Type | AC/DC Current AC/DC Voltage |
| Range | • High Current: ±10 VDC or 10 VAC • High Voltage: ±10 VDC or 10 VAC |
| Power | |
| Input Range | +10 VDC ~ +30 VDC |
| Consumption | 1.8 W |
| Mechanical | |
| Casing | Plastic |
| Dimensions (mm) | 103 x 94 x 29 (W x L x D) |
| Installation | DIN-Rail Mounting |
| Environment | |
| Operating Temperature | -25 ~ +75 °C |
| Storage Temperature | -30 ~ +75 °C |
| Humidity | 10 ~ 90% RH, Non-condensing |
Specifications as published by the manufacturer. Subject to change.
Σύνδεση