SC-6104-W5 Fan Coil Unit Controller, 4-ch Relay Output, RS-485
Three-speed fan coil unit controller with one isolated AC digital input, four power relay outputs and RS-485 for DCON or Modbus RTU. Suited to HVAC and lighting control.
- Controls fan coil units with local and remote relay ON/OFF switching
- Four form C power relays rated 20 A (NO) / 16 A (NC) at 250 VAC, recommended working current 5 A
- Isolated AC digital input, 90 ~ 240 VAC wet contact, 5000 Vrms isolation
- Temperature input for -40°C ~ +80°C thermistor, accuracy ±0.3°C at 25°C
- RS-485 with Modbus RTU or DCON protocol, software baud rates 1200 ~ 115200 bps
- Seven selectable coordinated DI/DO functions, no software needed to control the DO channels
102,00 € per piece
| 1–9 pcs | 102,00 € | |
|---|---|---|
| 10–30 pcs | 99,00 € | −3 % |
| 31+ pcs | 97,00 € | −5 % |
Πληροφορίες για το προϊόν "SC-6104-W5 Fan Coil Unit Controller, 4-ch Relay Output, RS-485"
SC-6104-W5 CR is a fan coil unit controller for HVAC and building automation. It switches four form C power relays from a single isolated AC digital input, so a fan speed sequence can run locally without a remote host controller. Relay status can also be monitored remotely over RS-485.
The module reads a thermistor temperature sensor covering -40°C to +80°C and makes the reading available over DCON or Modbus RTU. Seven coordinated DI/DO functions can be selected to suit the control logic. Each terminal has ±4 kV ESD protection, and the digital input is isolated from the module at 5000 Vrms.
Communication settings include a hardware-fixed baud rate of 9600 bps and software-configurable rates from 1200 to 115200 bps. DCON and Modbus RTU can use different addresses through hardware configuration. Do not switch loads above 550 W (5 A, 110 V) per channel, as this may cause the module to malfunction.
Applications
- Fan coil unit control in HVAC systems
- Building automation and HVAC control
- Lighting control
- Remote relay switching and status monitoring over RS-485
| Product type: | Fan coil unit controller |
|---|---|
| Interface: | RS-485 |
| Protocol: | DCON, Modbus RTU |
| Digital inputs: | 1 |
| Relay outputs: | 4 |
| Ports: | 1 |
| Isolation: | 5000 Vrms (DI) |
| Power input: | +10 ~ +30 VDC |
| Operating temperature: | -25 ~ +75 °C |
| Mounting: | DIN-rail |
| Housing: | Fireproof |
Specifications
| Software | |
|---|---|
| Function | Local and remote direct control relay ON/OFF and remote status monitoring. |
| EMS Protection | |
| EFT (IEC 61000-4-4) | ±1 kV for power and communication |
| ESD (IEC 61000-4-2) | ±4 kV contact for each terminal |
| LED Indicators | |
| Status | Power: 1 LED as Power Indicator Digital Output: 4 LED as digital output indicator |
| Temperature Measurement | |
| Channels | 1 |
| Range | -40°C ~ +80°C, Thermistor |
| Accuracy | ±0.3°C at 25°C, Max. ±2°C |
| Digital Input | |
| Channels | 1 |
| Type | Wet Contact, 90 ~ 240 VAC |
| ON Voltage Level | 85 VAC |
| OFF Voltage Level | 60 VAC |
| Isolation | 5000 Vrms |
| Input Impedance | 68 KΩ, 1 W |
| Relay Output | |
| Channels | 4 |
| Type | Power Relay, 4 Form C |
| Contact Rating | 20 A (NO)/16 A (NC) @ 250 VAC (Recommend Working Current 5 A) |
| Operate Time | 20 ms Max. |
| Release Time | 10 ms Max. |
| Electrical Endurance | 100,000 ops |
| Mechanical Endurance | 10,000,000 ops |
| Power on Value | Yes |
| COM Ports | |
| Ports | 1 x RS-485 |
| Baud Rate | Hardware Configuration: Fixed 9600 bps Software Configuration: 1200 ~ 115200 bps |
| Data Format | (N,8,1), (O,8,1), (E,8,1), (N,8,2) |
| Protocol | Modbus RTU or DCON |
| Power | |
| Input Range | +10 ~ +30 VDC |
| Consumption | 100 mA @ 24 VDC (2.4 W Max.) |
| Mechanical | |
| Dimensions (mm) | 116 x 122 x 64 (W x L x H) |
| Installation | DIN-Rail |
| Environment | |
| Operating Temperature | -25°C ~ +75°C |
| Storage Temperature | -30°C ~ +80°C |
| Humidity | 10 ~ 90% RH, Non-condensing |
Specifications as published by the manufacturer. Subject to change.