I-7012D 1-ch Analog Input Module with LED Display, DCON over RS-485
1-ch differential analog input module with 16-bit resolution, 5-digit LED display and RS-485 DCON interface for voltage and current measurement with 3000 VDC isolation.
- Single differential analog input for voltage (±150 mV to ±10 V) and current (±20 mA with external 125 Ω resistor)
- 16-bit resolution with normal mode accuracy of ±0.05% of FSR at 10 Hz sampling
- 5-digit, 7-segment LED display for local readout
- 50 Hz event counter on the digital input (max. 65535 counts)
- Two open-collector sink digital outputs, 30 mA per channel, for high/low alarms
- RS-485 interface with DCON protocol, 1200 ~ 115200 bps, data format (N, 8, 1)
237,00 € per piece
| 1–9 pcs | 237,00 € | |
|---|---|---|
| 10–30 pcs | 230,00 € | −3 % |
| 31+ pcs | 225,00 € | −5 % |
Πληροφορίες για το προϊόν "I-7012D 1-ch Analog Input Module with LED Display, DCON over RS-485"
The I-7012D CR is a DIN-rail analog input module for measuring voltage and current signals and passing the results to a host over RS-485 using the DCON protocol. It suits engineers who need a single differential input with 16-bit resolution, a local readout and simple alarm outputs within an I-7000 remote I/O system.
The module provides one differential analog input with several voltage ranges from ±150 mV to ±10 V, plus a ±20 mA current range that needs an optional external 125 Ω resistor. Normal mode sampling runs at 10 Hz with an accuracy of ±0.05% of FSR. The single digital input can be used as a 50 Hz event counter, and two open-collector digital outputs support high/low alarm functions.
The D version adds a 5-digit, 7-segment LED display for local indication. Intra-module isolation is rated at 3000 VDC, and the unit operates from +10 ~ +30 VDC with reverse polarity protection across a -25 ~ +75 °C operating range.
Applications
- Building Automation
- Factory Automation
- Machine Automation
- Remote Maintenance
- Remote Diagnosis
- Testing Equipment
| Product type: | Analog Input Module |
|---|---|
| Interface: | RS-485 |
| Protocol: | DCON |
| Digital inputs: | 1 |
| Digital outputs: | 2 |
| Analog inputs: | 1 |
| Ports: | 1 |
| Isolation: | 3000 VDC |
| Power input: | +10 ~ +30 VDC |
| Operating temperature: | -25 ~ +75 °C |
| Mounting: | DIN-rail |
Specifications
| CPU Module | |
|---|---|
| Watchdog Timer | Module, Communication (Programmable) |
| Display | |
| Type | 5-Digit 7 Segment LED Display (Only for I-7012FD, I-7012D) |
| Isolation | |
| Intra-module Isolation | 3000 VDC |
| EMS Protection | |
| EFT (IEC 61000-4-4) | ±4 kV for Power Line |
| ESD (IEC 61000-4-2) | ±2 kV Contact for Each Terminal |
| Surge (IEC 61000-4-5) | ±0.5 kV for Power Line |
| LED Indicators | |
| Status | 1 x Power and Communication |
| Analog Input | |
| Channels | 1 Differential |
| Type | Voltage Current |
| Range | Voltage: ±150 mV, ±500 mV, ±1 V, ±5 V, ±10 V Current: ±20 mA (requires an optional external 125 Ω resistor) |
| Resolution | 16-bit |
| Accuracy | I-7012F(D) Normal Mode: ±0.05% of FSR Fast Mode: ±0.25% of FSR I-7012(D) Normal Mode: ±0.05% of FSR |
| Sampling Rate | I-7012F(D) Normal Mode: 10 Hz Fast Mode: 100 Hz I-7012(D) Normal Mode: 10 Hz |
| Input Impedance | 20 MΩ |
| Common Voltage Protection | ±100 VDC |
| Overvoltage Protection | ±120 VDC |
| Digital Input/Counter | |
| Channels | 1 |
| Type | Dry Contact |
| Sink/Source (NPN/PNP) | Source |
| ON Voltage Level | Close to GND |
| OFF Voltage Level | Open |
| Max. Counts | 65535 (16-bit) |
| Frequency | 50 Hz |
| Input Impedance | 3 kΩ |
| Overvoltage Protection | ±30 VDC |
| Digital Output | |
| Channels | 2 |
| Type | Open Collector |
| Sink/Source (NPN/PNP) | Sink |
| Load Voltage | +3.5 ~ +30 VDC |
| Load Current | 30 mA/channel |
| Power on Value | Programmable |
| Safe Value | Programmable |
| COM Ports | |
| Ports | 1 x RS-485 |
| Baud Rate | 1200 ~ 115200 bps |
| Data Format | (N, 8, 1) |
| Protocol | DCON |
| Power | |
| Reverse Polarity Protection | Yes |
| Input Range | +10 ~ +30 VDC |
| Consumption | I-7012/12F: 1.3 W I-7012D/12FD: 1.9 W |
| Mechanical | |
| Dimensions (mm) | 72 x 123 x 35 (W x L x H) |
| Installation | DIN-Rail Mounting |
| Environment | |
| Operating Temperature | -25 ~ +75 °C |
| Storage Temperature | -40 ~ +85 °C |
| Humidity | 10 ~ 95% RH, Non-condensing |
Specifications as published by the manufacturer. Subject to change.