HRT-310 Modbus RTU/ASCII to HART Gateway, 1-Port HART Master
Modbus RTU/ASCII to HART gateway that lets a Modbus master read HART devices such as transmitters and actuators, supporting up to 15 devices per port. DIN-rail or wall mounting.
- Modbus RTU and ASCII support in Modbus slave mode, with RS-232 (3-wire), RS-422 and RS-485 serial interfaces
- Point-to-point or multi-drop HART operation for up to 15 HART devices, with HART short and long frame support
- Burst mode support and the ability to allow two HART masters
- Loop power output of +30 V for 2-wired or 4-wired HART devices, with the loop resistor set by DIP switch
- On-line replacement of HART devices and automatic acquisition of long frame addresses
- Built-in watchdog and LED indicators for status monitoring
390,00 € per piece
| 1–9 pcs | 390,00 € | |
|---|---|---|
| 10–30 pcs | 379,00 € | −3 % |
| 31+ pcs | 371,00 € | −5 % |
Πληροφορίες για το προϊόν "HRT-310 Modbus RTU/ASCII to HART Gateway, 1-Port HART Master"
HRT-310 CR is a HART master to Modbus slave gateway. It lets a Modbus master access HART field devices, such as transmitters and actuators, so their data can be brought into an existing Modbus network without custom HART handling. The HG_Tool software is provided for module configuration and HART device diagnosis.
The gateway supports HART short and long frames, burst mode and point-to-point or multi-drop topologies, with up to 15 HART devices. Two HART masters can be allowed, and HART devices can be replaced on-line. The Modbus side offers RTU and ASCII formats in slave mode over RS-232 (3-wire), RS-422 or RS-485.
Typical use is integrating HART flow meters into an HMI or SCADA system. Each HART device appears to the host as a Modbus slave, so the host can use its built-in Modbus RTU communication to read the devices directly.
Applications
- Industrial automation
- Factory automation
- Process automation
- Integrating HART flow meters and other HART devices into HMI or SCADA systems via Modbus
- Connecting HART devices to Modbus networks in multi-channel RS-485 installations
| Product type: | Gateway |
|---|---|
| Interface: | RS-232 / RS-422 / RS-485 |
| Protocol: | Modbus RTU / Modbus ASCII / HART |
| Ports: | 1 HART |
| Isolation: | UL1577 |
| Power input: | +10 ~ +30 VDC |
| Operating temperature: | -25 ~ +75 °C |
| Mounting: | DIN-rail |
Specifications
| COM Ports | |
|---|---|
| Ports | RS-232(3 wires) / RS-422 / RS-485 |
| Baud Rate | 1200, 2400, 4800, 9600, 19200, 38400, 57600, 115200 |
| Protocol | Modbus RTU / Modbus ASCII |
| HART | |
| Ports | 1 |
| Device | 2-wired or 4-wired HART devices |
| Topology | Point to Point or Multi-Drop |
| Data | Only Digital Data |
| Frame Type | Short and Long Frame |
| Burst Mode | Supported |
| Max. HART Device | 15 |
| Loop Resistor | 250 Ω (1W) by Dip-Switch |
| Isolation | UL1577 Spec. |
| Protocol | 2-pin screwed terminal block |
| Loop Power | Yes (module provides +30V output) |
| Power | |
| Reverse Polarity Protection | Power reverse polarity protection, Over-voltage brown-out protection |
| Input Range | Unregulated +10 ~ +30 VDC |
| Consumption | 3.5W (Max.) |
| Mechanical | |
| Dimensions (mm) | 25 x 116 x 120 (W x L x H) |
| Installation | DIN-Rail |
| Environment | |
| Operating Temperature | -25 ~ +75 °C |
| Storage Temperature | -30 ~ +80 °C |
| Humidity | 10% ~ 90% RH, Non-condensing |