PM-3112-100P Single-Phase Power Meter, Modbus RTU, 2 Loops, 60 A CT

Informace o výrobku "PM-3112-100P Single-Phase Power Meter, Modbus RTU, 2 Loops, 60 A CT"

PM-3112-100P CR is a two-loop single-phase power meter for measuring true RMS voltage, current and power on 1P2W circuits. Each loop has its own reference voltage and current input, so engineers can monitor two independent loops from one DIN-rail unit and read the results over Modbus RTU.

This variant includes two 60 A clip-on current transformers with a 10 mm inside diameter and 4 m wire leads, which suits smaller conductors and makes retrofit installation straightforward without disconnecting the load. Input voltage range is 10 ~ 300 VAC and the meter reports a wide set of parameters, including active, apparent and reactive power and energy, power factor and frequency, updated every second.

Two Form A power relay outputs allow the meter to drive sirens or indicator lights for alarm messages. The unit is powered from +12 ~ 48 VDC and is rated for an operating temperature of -20 ~ +70 °C.

Applications

  • Generator monitoring
  • Switchgear distribution systems
  • Energy management
Product type: Power meter
Interface: RS-485
Protocol: Modbus RTU
Relay outputs: 2
Ports: 1 x RS-485
Isolation: 3000 VDC
Power input: +12 ~ 48 VDC
Operating temperature: -20 ~ +70 °C
Mounting: DIN-rail
Housing: Plastic

Specifications

AC Power Measurement
Wiring1P2W-1CT
Loops1-phase: 2
Input Voltage10 ~ 300 V
Input CurrentPM-3112-100: CTØ10 mm (0.05 A ~ 60 A)
PM-3112-100P: CTØ10 mm (0.05 A ~ 60 A)
PM-3112-160: CTØ16 mm (0.1 A ~ 100 A)
PM-3112-160P: CTØ16 mm (0.1 A ~ 100 A)
PM-3112-240: CTØ24 mm (0.15 A ~ 200 A)
PM-3112-240P: CTØ24 mm (0.15 A ~ 200 A)
Input Frequency50/60 Hz
W AccuracyBetter than 0.5% (PF=1)
Power Parameter MeasurementTrue RMS voltage (Vrms), True RMS current (Irms), Active Power (kW), Active Energy (kWh), Apparent Power (kVA), Apparent Energy (kVAh), Reactive Power (kVAR), Reactive Energy (kVARh), Power Factor (PF), Frequency
Data Update Rate1 Second
Relay Output
Channels2
TypePower Relay
Contact RatingForm A:
5 A @ 250 VAC
5 A @ 30 VDC
COM Ports
Ports1 x RS-485
Baud Rate9600, 19200 (default), 38400, 115200; DIP Switch Selectable
Data FormatN,8,1 (default); N,8,2; E,8,1; E,8,2; O,8,1; O,8,2
ProtocolModbus RTU
Isolation3000 VDC
Power
Input Range+12 ~ 48 VDC
Consumption2W
Mechanical
CasingPlastic
Dimensions (mm)33 x 127 x 100 (W x L x H)
InstallationDIN-Rail Mounting
Environment
Operating Temperature-20 ~ +70 °C
Storage Temperature-25 ~ +80 °C
Humidity10 ~ 90% RH, Non-condensing

Specifications as published by the manufacturer. Subject to change.