M-7017RMS-G 8-ch True RMS Analog Input Module, RS-485 Modbus RTU/DCON
Eight differential True RMS input channels convert AC signals from 150 mVrms to 10 Vrms into DC values, with RS-485 communication over Modbus RTU or DCON.
- Eight differential True RMS inputs with individually configurable ranges from 0 ~ +150 mVrms to 0 ~ +10 Vrms
- 16-bit resolution with ±0.15% of FSR accuracy at 50/60 Hz and ±0.5% of FSR across 45 Hz to 10 kHz for sinusoidal signals
- Accurate True RMS measurement of non-sinusoidal waveforms, with ±0.2% of FSR at crest factor 1 to 2
- 2500 VDC intra-module isolation and ±35 VDC overvoltage protection
- Single RS-485 port supporting Modbus RTU and DCON, 1200 ~ 115200 bps
- Power input of +10 ~ +30 VDC with reverse polarity protection, 0.9 W consumption
261,00 € per piece
| 1–9 pcs | 261,00 € | |
|---|---|---|
| 10–30 pcs | 253,00 € | −3 % |
| 31+ pcs | 248,00 € | −5 % |
Информация за продукта "M-7017RMS-G 8-ch True RMS Analog Input Module, RS-485 Modbus RTU/DCON"
The M-7017RMS-G CR is an RS-485 remote I/O module for measuring AC signals. It provides eight differential inputs that calculate the True RMS value of complex waveforms and report the result as a DC value, so the measurement stays accurate on non-sinusoidal signals as well as pure sine waves.
Each channel can be configured individually across five input ranges, from 0 ~ +150 mVrms up to 0 ~ +10 Vrms. The module is factory calibrated with ±0.15% accuracy at 50/60 Hz and supports standard operating frequencies from 45 Hz to 10 kHz. Built-in 2500 VDC intra-module isolation and ±35 VDC overvoltage protection help protect the module and the wider system.
The module is configured and read over a single RS-485 port using Modbus RTU or DCON at baud rates from 1200 to 115200 bps. It runs from a +10 ~ +30 VDC supply with reverse polarity protection, mounts on a DIN rail and operates from -25 ~ +75 °C. The grey-cover variant is suited to panel installations in building, factory and machine automation.
Applications
- Building Automation
- Factory Automation
- Machine Automation
- Remote Maintenance
- Remote Diagnosis
- Testing Equipment
| Product type: | Analog Input Module |
|---|---|
| Interface: | RS-485 |
| Protocol: | DCON, Modbus RTU |
| Analog inputs: | 8 |
| Ports: | 1 |
| Isolation: | 2500 VDC |
| Power input: | +10 ~ +30 VDC |
| Operating temperature: | -25 ~ +75 °C |
| Mounting: | DIN-rail |
| Housing: | Gray cover |
Specifications
| CPU Module | |
|---|---|
| Watchdog Timer | Module, Communication (Programmable) |
| Isolation | |
| Intra-module Isolation | 2500 VDC |
| EMS Protection | |
| EFT (IEC 61000-4-4) | ±4 kV for Power Line |
| ESD (IEC 61000-4-2) | ±4 kV Contact for Each Terminal ±8 kV Air for Random Point |
| Surge (IEC 61000-4-5) | ±0.5 kV for Power Line |
| LED Indicators | |
| Status | 1 x Power and Communication |
| Analog Input | |
| Channels | 8 Differential |
| Type | True RMS |
| Range | 0 ~ +10 Vrms, 0 ~ +5 Vrms, 0 ~ +1 Vrms, 0 ~ +500 mVrms, 0 ~ +150 mVrms |
| Resolution | 16-bit |
| Accuracy | • Sinusoid: 50/60 Hz: ±0.15% of FSR 45 Hz to 10 kHz: ±0.5% of FSR • Non-Sinusoid: Crest Factor = 1 to 2: ±0.2% of FSR Crest Factor = 2 to 3: ±0.35% of FSR • DC: 0 ~ +10 V/0 ~ +5 V/0 ~ +1 V: ±0.3% of FSR 0 ~ +500 mV, 0 ~ +150 mV: ±0.7% of FSR |
| Sampling Rate | 10 Hz (Total) |
| Input Impedance | >2 MΩ |
| Overvoltage Protection | ±35 VDC |
| Individual Channel Configuration | Yes |
| COM Ports | |
| Ports | 1 x RS-485 |
| Baud Rate | 1200 ~ 115200 bps |
| Data Format | (N, 8, 1), (N, 8, 2), (E, 8, 1), or (O, 8, 1) |
| Protocol | Modbus RTU, DCON |
| Power | |
| Reverse Polarity Protection | Yes |
| Input Range | +10 ~ +30 VDC |
| Consumption | 0.9 W |
| Mechanical | |
| Dimensions (mm) | 72 x 123 x 35 (W x L x H) |
| Installation | DIN-Rail Mounting |
| Environment | |
| Operating Temperature | -25 ~ +75 °C |
| Storage Temperature | -40 ~ +85 °C |
| Humidity | 10 ~ 95% RH, Non-condensing |
Specifications as published by the manufacturer. Subject to change.
Downloads
Вход